PROTECTIVE FUNCTIONS

 

 

 

 

 

 

 

 

 

 

Operation Panel

E.OC3

 

FR-PU04

 

OC During Dec

 

 

Indication

 

 

 

 

 

 

 

 

 

 

 

 

Name

Overcurrent shut-off during deceleration

 

 

 

 

When the inverter output current reaches or exceeds approximately 150% of the

 

 

Description

rated current during deceleration (other than acceleration or constant speed),

 

 

 

the protective circuit is activated to stop the inverter output.

 

 

 

Check for sudden speed reduction.

 

 

 

Check point

Check for output short circuit.

 

 

 

 

Check for too fast operation of motor's mechanical brake.

 

 

Corrective action

Increase the deceleration time.

 

 

 

Check mechanical brake operation.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Operation Panel

E.OV1

 

FR-PU04

 

OV During Acc

 

 

Indication

 

 

 

 

 

 

 

 

 

 

 

 

Name

Regenerative overvoltage shut-off during acceleration

 

 

 

If regenerative energy causes the inverter's internal main circuit DC voltage to

 

 

Description

reach or exceed the specified value, the protective circuit is activated to stop the

 

 

inverter output. It may also be activated by a surge voltage generated in the

 

 

 

 

 

 

power supply system.

 

 

 

 

 

Check point

Check for too slow acceleration.

 

 

 

Corrective action

Decrease the acceleration time.

 

 

 

 

 

 

 

 

 

 

 

 

Operation Panel

E.OV2

 

FR-PU04

 

Stedy Spd OV

 

 

Indication

 

 

 

 

 

 

 

 

 

 

 

 

Name

Regenerative overvoltage shut-off during constant speed

 

 

 

If regenerative energy causes the inverter's internal main circuit DC voltage to

 

 

Description

reach or exceed the specified value, the protective circuit is activated to stop the

 

 

inverter output. It may also be activated by a surge voltage generated in the

 

 

 

 

 

 

power supply system.

 

 

 

 

 

Check point

Check for sudden load change.

 

 

 

Corrective action

Keep load stable.

 

 

 

 

 

Use the brake unit or power regeneration converter (FR-RC) as required.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Operation Panel

E.OV3

 

FR-PU04

 

OV During Dec

 

 

Indication

 

 

 

 

 

 

 

 

 

 

 

 

Name

Regenerative overvoltage shut-off during deceleration or stop

 

 

 

If regenerative energy causes the inverter's internal main circuit DC voltage to

 

 

Description

reach or exceed the specified value, the protective circuit is activated to stop the

 

 

inverter output. It may also be activated by a surge voltage generated in the

 

 

 

 

 

 

power supply system.

 

 

 

 

 

Check point

Check for sudden speed reduction.

 

 

 

 

Increase the deceleration time. (Set the deceleration time which matches the

 

 

Corrective action

 

inertia moment of the load.)

 

 

 

Decrease the braking duty.

 

 

 

 

 

 

 

 

Use the brake unit or power regeneration converter (FR-RC) as required.

 