Mitsumi electronic 55K, FR-F520-0.75K Advanced PID control Pr to Pr NA, EC versions only

Models: FR-F520-0.75K 55K

1 217
Download 217 pages 2.41 Kb
Page 158
Image 158

PARAMETERS

4.2.54 Advanced PID control (Pr. 500 to Pr. 516) (NA, EC versions only)

Pr. 500

"Auxiliary motor operation selection"

 

Related parameters

 

 

 

 

Pr. 501

"Motor switch-over selection"

Pr. 128 to Pr.134 (PID control)

Pr. 180 to Pr. 186

Pr. 502

"MC switching interlock time"

 

(input terminal assignment)

Pr. 190 to Pr. 195

Pr. 503

"Start waiting time"

 

(output terminal assignment)

 

 

 

Pr. 504 "Auxiliary motor connection-time deceleration time"

Pr. 505 "Auxiliary motor disconnection-time acceleration time"

Pr. 506 "Output stop detection time"

Pr. 507 "Output stop detection level"

Pr. 508 "Output stop cancel process value level"

Pr. 509 "Auxiliary motor 1 starting frequency"

Pr. 510 "Auxiliary motor 2 starting frequency"

Pr. 511 "Auxiliary motor 3 starting frequency"

Pr. 512 "Auxiliary motor 1 stopping frequency"

Pr. 513 "Auxiliary motor 2 stopping frequency"

Pr. 514 "Auxiliary motor 3 stopping frequency"

Pr. 515 "Auxiliary motor start delay frequency"

Pr. 516 "Auxiliary motor stop delay frequency"

With the advanced PID control functions, you can control pumps/fans using several motors (maximum of 4

 

motors).

4

 

<Operation outline>

#Set the number of commercial power supply operation motors in Pr. 500 "auxiliary motor operation selection", and the motor switch-over method in Pr. 501 "motor switch-over selection".

Pr. Number

Name

Setting Range

Setting Increments

Factory Setting

Description

 

 

 

 

 

Set the number of auxiliary

500

Auxiliary motor

0 to 3

1

0

motors to be run. (1 to 3

operation selection

motors)

 

 

 

 

 

 

 

 

 

0: Auxiliary motors are not run.

 

Motor switch-over

 

 

 

0: Basic Method

501

0 to 2

1

0

1: Alternative Method

selection

 

 

 

 

2: Direct Method

 

 

 

 

 

145

Page 158
Image 158
Mitsumi electronic 55K, FR-F520-0.75K instruction manual Advanced PID control Pr to Pr NA, EC versions only