INSTALLATION AND WIRING

2.3.7 Instructions for compliance with U.S. and Canadian Electrical Codes

(Standard to comply: UL 508C) (1) Installation

The above types of inverter have been approved as products for use in enclosure and approval tests were conducted under the following conditions.

200V class

 

 

 

Air Vent Area

External Cooling Fan

 

 

Minimum Enclosure Volume

(The following number of

 

 

(Ratio of air vent area in

 

Inverter Model

(Ratio of enclosure volume to

fans of 100cfm wind pressure

 

enclosure top and bottom to

 

 

inverter volume)

are installed 10cm above the

 

 

enclosure surface area)

 

 

 

inverter top)

 

 

 

 

 

FR-F520-0.75K

150

5.8

0

 

FR-F520-1.5K

245

1.5

1

 

FR-F520-2.2K

245

1.5

1

 

FR-F520-3.7K

245

1.5

1

 

FR-F520-5.5K

245

1.5

1

 

FR-F520-7.5K

245

1.5

1

 

FR-F520-11K

245

1.5

1

 

FR-F520-15K

370

2.6

2

 

FR-F520-18.5K

370

2.6

2

 

FR-F520-22K

370

2.6

2

 

FR-F520-30K

2

 

FR-F520-37K

2

 

FR-F520-45K

2

 

FR-F520-55K

2

 

400V class

 

 

 

Design the enclosure so that the ambient temperature, humidity and ambience of the inverter will satisfy the above specifications. (Refer to page 187)

(2) Branch circuit protection

For installation in United States, branch circuit protection must be provided, in accordance with the National Electrical Code and any applicable local codes.

For installation in Canada, branch circuit protection must be provided in accordance with the Canada Electrical Code and any applicable provincial codes.

(3) Short circuit ratings

200V class

Suitable For Use in A Circuit Capable of Delivering Not More Than 5 or 10kA rms Symmetrical Amperes, 230 or 500 Volts Maximum.

400V class

Suitable For Use in A Circuit Capable of Delivering Not More Than 10kA rms Symmetrical Amperes, 500 Volts Maximum.

(4) Wiring of the power supply and motor

Screw the cables wired to the input (R, S, T) <L1, L2, L3> and output (U, V, W) terminals and control circuit of the inverter to the specified tightening torque using UL-recognized, 75° or higher rated copper wires and round crimping terminals. Crimp the crimping terminals with the crimping tool recommended by the terminal maker.

39

Page 50
Image 50
Mitsumi electronic 55K Standard to comply UL 508C 1 Installation, Branch circuit protection, Short circuit ratings