Mitsumi electronic FR-F520-0.75K, 55K Option slot alarm 1 to, To OP3, Corrupt Memry

Models: FR-F520-0.75K 55K

1 217
Download 217 pages 2.41 Kb
Page 181
Image 181
Operation Panel
Indication
Name
Description
Check point
Corrective action
Operation Panel
Indication
Name
Description
Check point
Corrective action

PROTECTIVE FUNCTIONS

E.OLT

FR-PU04

Stll Prev STP (OL shown during stall

prevention operation)

Stall prevention

The running frequency has fallen to 0 by stall prevention activated. (OL while stall prevention is being activated.)

Check the motor for use under overload.

Reduce the load weight.

E.OPT

FR-PU04

Option Fault

Option alarm

Stops the inverter output if two or more communication options are fitted. (Note 4)

When the high power factor converter is connected, this alarm appears if an AC power supply is accidentally connected to R, S, T <L1, L2, L3>.

Check that the number of communication options fitted is one.

When the high power factor converter is connected, check for an AC power supply connected to the R, S, T <L1, L2, L3> terminals.

Reduce the communication options used to one.

Check the parameter (Pr. 30) setting and wiring.

When the high power factor converter is connected, connecting an AC power supply to the R, S, T <L1, L2, L3> terminals may have damaged the inverter. Contact your sales representative.

Note 4: The FR-A5NR (relay output/computer link) allows you to fit one more communication option. In this case, only the relay output function may be used and the computer link function is unusable.

Operation Panel

E.OP1

 

FR-PU04

Option slot alarm 1 to 3

Indication

to OP3

 

 

 

 

 

 

 

 

 

Name

Option slot alarm

 

 

 

Stops the inverter output if a functional alarm occurs in the plug-in option loaded

Description

in the corresponding slot (e.g. communication alarm of the communication

 

option, contact fault of the plug-in option other than a communication option)

Check for a wrong option function setting and operation.

Check that the plug-in option is connected to the connector securely.

Check point

(1 to 3 indicate the option slot numbers.)

Check the communication cable for wire breakage.

Check that the termination resistor is fitted properly.

Corrective action

Confirm the option function setting, etc.

 

Connect the plug-in option securely.

 

 

 

 

 

 

 

 

 

 

Operation Panel

 

E.PE

 

FR-PU04

 

Corrupt Memry

Indication

 

 

 

 

 

 

 

 

 

Name

Parameter storage device alarm

 

Description

Stops the inverter output if a fault occurs in the E2PROM device which stores

parameter settings.

 

 

 

 

 

 

 

Check point

Check for too many number of parameter write times.

Corrective action

Change the inverter.

 

 

 

167

Page 181
Image 181
Mitsumi electronic FR-F520-0.75K Option slot alarm 1 to, To OP3, Check for a wrong option function setting and operation