PARAMETERS

<Output stop detection>

Process value

Pr. 508: Output stop cancel level

Time

Output frequency

Pr. 507: Output stop level

Pr. 506: Output stop

 

detection time

Output at stop

Td

 

Time

Motor

STOPSTART

#The output stops if the output frequency continues to be lower than the Pr. 507 value for longer than the time set in Pr. 506.

When the setting is 9999, the output stop function is not performed.

Also, an output stop is not detected when the process value is not more than the Pr. 508 value or when the start signal is off. It is not detected during auxiliary motor operation either.

Parameter Number

Name

Setting Range

Setting Increments

Factory Setting

506

Output stop detection time

0 to 3600s, 9999

0.1s

9999

#You can set the set the output frequency value at which an output stop is detected. The output is stopped when the output frequency continues to be lower than the Pr. 507 value for longer than the time set in Pr. 506.

Parameter Number

Name

Setting Range

Setting Increments

Factory Setting

507

Output stop detection level

0 to 120Hz

0.01Hz

0Hz

#You can set the process value at which a restart is made after the output stop. Set the ratio of the process value to the set point.

Parameter Number

Name

Setting Range

Setting Increments

Factory Setting

508

Output stop cancel process value

0 to 100%

0.1%

100%

level

 

 

 

 

152