SPECIFICATIONS

6.1.2 Common specifications

 

Control system

 

Soft-PWM control/high carrier frequency PWM control (V/F control), Optimum excitation

 

 

control

 

 

 

 

 

 

 

 

 

Output frequency range

0.5 to 120Hz

 

 

Frequency

 

Analog input

0.015Hz/60Hz (terminal 2 input: 12 bits/0 to 10V, 11 bits/0 to 5V, terminal 1 input: 12 bits/-10

specifications

setting

 

to +10V, 11 bits/-5 to +5V)

 

 

 

 

Voltage/frequency

 

Base frequency set as required between 0 and 120Hz. Constant torque or variable torque

 

resolution

 

Digital input

0.01Hz

 

 

Frequency accuracy

Within ± 0.2% of maximum output frequency (25° C ± 10° C for analog input, within 0.01% of set

 

output frequency for digital input

 

 

 

 

 

 

 

 

Control

characteristic

 

pattern can be selected.

 

Torque boost

 

Manual and automatic torque boosts

 

 

 

 

 

Acceleration/deceleration

0 to 3600 s (acceleration and deceleration can be set individually), linear or S-pattern

 

time setting

 

acceleration/deceleration mode can be selected.

 

 

DC injection brake

Operation frequency (0 to 120Hz), operation time (0 to 10 s), voltage (0 to 30%) variable

 

Stall prevention operation

Operation current level can be set (0 to 150% variable), presence or absence can be selected.

 

level

 

 

 

 

 

 

 

 

 

 

Frequency

 

Analog input

0 to 5VDC, 0 to 10VDC, 0 to ± 10VDC, 4 to 20mADC

 

 

setting

 

Digital input

3-digit BCD or 12-bit binary using operation panel or parameter unit (when the FR-A5AX option

 

signal

 

 

is used)

 

 

 

 

 

 

 

Start signal

 

Available individually for forward rotation and reverse rotation. Start signal self-holding input (3-

 

 

wire input) can be selected.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Up to 7 speeds can be selected. (Each speed can be set between 0 and

 

 

 

 

Multi-speed selection

120Hz, running speed can be changed during operation from the PU

 

 

 

 

 

 

 

(FR-DU04/FR-PU04).)

 

 

 

 

Second acceleration/

0 to 3600 s (up to two different acceleration and deceleration times can be set

 

 

 

 

deceleration time

 

 

 

 

individually.)

 

 

 

 

selection

 

 

 

 

 

 

 

 

 

 

 

Jog operation

Provided with jog operation mode select terminal (Note 1)

 

 

 

 

selection

 

 

 

 

 

 

 

 

 

 

 

Current input selection

Input of frequency setting signal 4 to 20mADC (terminal 4) is selected.

 

 

 

 

Selection of automatic

 

 

 

signals

 

restart after an

Selection of whether automatic restart is made or not after an instantaneous

Use Pr. 180

 

 

instantaneous power

power failure

 

 

selection.

 

 

 

failure

 

 

to Pr. 186 for

 

 

 

 

 

 

 

Input

 

External thermal relay

Thermal relay contact input when the thermal relay provided externally is

 

specifications

 

input

 

used to stop the inverter

 

 

FR-HC connection

Inverter operation enable input and instantaneous power failure detection

 

 

 

 

 

 

 

 

input

 

 

 

 

 

 

 

 

 

 

 

External DC dynamic

External input for DC dynamic braking start

 

 

 

 

braking start signal

 

 

 

 

 

 

Operational

 

 

PID control valid

Selection for exercising PID control

 

 

 

PU-external operation

External interlock switch-over of PU operation

 

 

 

 

switch-over

External selection between PU and external operation

 

 

 

 

PU operation external

 

 

 

 

 

interlock

 

 

 

 

 

 

Output stop

Instantaneous shut-off of inverter output (frequency, voltage)

 

 

 

 

Alarm reset

Alarm retained at the activation of protective function is reset.

 

 

 

 

 

 

 

Maximum/minimum frequency setting, frequency jump operation, external thermal relay input

 

Operation functions

selection, polarity reversible operation, automatic restart operation after instantaneous power

 

failure, commercial power supply-inverter switch-over operation, forward/reverse rotation

 

 

 

 

 

 

 

 

 

 

 

 

prevention, operation mode selection, PID control, computer link operation (RS-485)

 

 

 

 

 

 

5 different signals can be selected from inverter running, up to frequency, instantaneous power

 

 

 

 

 

 

failure (undervoltage), frequency detection, second frequency detection, during PU operation,

 

 

 

Operating status

overload alarm, electronic overcurrent protection pre-alarm, zero current detection, PID lower

 

 

 

limit, PID upper limit, PID forward/reverse rotation, commercial power supply-inverter switch-

 

signals

 

 

 

 

 

 

 

 

 

over MC1, 2, 3, operation ready, fan fault and fin overheat pre-alarm minor fault. Open

 

 

 

 

 

 

 

 

 

 

 

 

collector output.

 

 

Output

 

Alarm (inverter trip)

Contact output...change-over contact (230VAC 0.3A, 30VDC 0.3A) Open collector...alarm

 

 

code (4 bit) output

 

 

 

 

 

 

 

 

 

 

 

 

1 signal can be selected from output frequency, motor current (steady or peak value), output

 

 

 

 

 

 

voltage, frequency setting, running speed, converter output voltage (steady or peak value),

 

 

 

For meter

 

electronic overcurrent protection load factor, input power, output power, load meter and

 

 

 

 

 

 

reference voltage output. Pulse train output (1440 pulses/s/full scale) and analog output (0 to

 

 

 

 

 

 

10VDC).

 