PARAMETERS

7)Sum check code

The sum check code is 2-digit ASCII (hexadecimal) representing the lower 1 byte (8 bits) of the sum (binary) derived from the checked ASCII data.

(Example1)

 

 

Station

 

Instruction

*Waiting time

 

 

 

 

Sum check

 

 

ComputerInverter

ENQ

 

 

 

Data

 

 

 

 

number

 

code

 

 

 

code

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

 

 

 

1

 

E

1

1

0

7

A

D

F

4

Binary code

ASCII code

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

H05

 

H30

H31

 

H45

H31

H31

H30

H37

H41

H44

H46

H34

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

H

H

H H

H

H

H H

H

 

 

 

 

 

 

 

 

30 + 31 + 45 + 31 + 31 + 30 + 37 + 41 + 44

 

 

 

 

 

 

 

 

 

 

H

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

=1F4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Sum

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*When Pr. 123 "waiting time setting" 9999, create the communication request data with no "waiting time" in the data format. (The number of characters is decreased by 1.)

(Example2)

 

 

Station

 

 

 

 

 

 

Sum check

 

 

InverterComputer

STX

 

 

 

Read data

 

ETX

 

 

 

 

 

number

 

 

 

 

 

 

code

 

 

 

 

 

0

 

 

 

1

 

1

7

7

0

 

3

0

Binary code

 

ASCII code

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

H02

 

H30

H31

 

H31

H37

H37

H30

H03

H33

H30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

H

H

H H

H

H

 

 

 

 

 

 

 

 

30 + 31 + 31 + 37 + 37 + 30

 

 

 

 

 

 

 

 

 

H

 

 

 

 

 

 

 

 

 

 

 

 

 

=130

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Sum

 

 

 

 

 

 

 

 

 

 

 

 

8)Error code

If any error is found in the data received by the inverter, its definition is sent back to the computer together with the NAK code. (Refer to page 118)

Note: 1. When the data from the computer has an error, the inverter will not accept that data.

2.Any data communication, e.g. run command, monitoring, is started when the computer gives a communication request. Without the computer's command, the inverter does not return any data. For monitoring, therefore, design the program to cause the computer to provide a data read request as required.

3.Data for link parameter expansion setting differs as indicated below between access to Pr. 0 to Pr. 99 values and access to Pr. 100 to Pr. 905:

 

 

Instruction

Data

 

 

Code

 

 

 

 

 

 

H00: Pr. 0 to Pr. 79 values are accessible.

 

Read

H7F

H01: Pr. 100 to Pr. 158 and Pr. 900 to Pr. 905 values are

 

 

 

accessible.

Link parameter

 

 

H02: Pr. 160 to Pr. 244 values are accessible.

 

 

expansion setting

 

 

H03: Pr. 300 to Pr. 348 values are accessible.

 

Write

HFF

H05: Pr. 500 to Pr. 516 values are accessible.

 

 

 

(NA, EC versions only)

 

 

 

H09: Pr. 990 and Pr.991 values are accessible.

114