OPERATION/CONTROL

3.4.2 External operation mode (Operation using external input signals)

(1) Operation at 60Hz

Step

Description

 

Image

 

 

 

Power-on Operation mode check

 

 

 

 

 

Switch power on and make sure that the operation command indication "EXT" is lit.

ON

 

 

 

 

(If it is not lit, press the MODE key to choose the operation mode and press the

 

 

 

 

1

key to switch to external operation. For operation mode changing, refer to

 

FR-DU04

CONTROL PANEL

 

page 49.)

 

 

 

Hz

 

 

 

 

A

 

 

 

 

 

V

 

 

 

MON

EXT

PU

 

 

 

 

REV

FWD

 

Start

 

 

 

 

 

Turn on the start switch (STF or STR).

Forward

 

 

 

 

The operation status indication "FWD" or "REV" flickers.

rotation Reverse

 

 

 

 

 

rotation

 

 

2

Note: The motor does not start if both the forward and reverse

 

FR-DU04

CONTROL PANEL

 

rotation switches are turned on.

 

 

 

Hz

 

 

 

 

 

A

 

If both switches are turned on during operation, the motor

 

 

 

V

 

 

 

REV

FWD

 

 

 

MON

EXT

PU

 

decelerates to a stop.

 

 

 

 

 

Acceleration Constant speed

 

 

 

 

 

Slowly turn the potentiometer (frequency setting potentiometer) full clockwise.

 

 

 

 

 

The frequency shown on the display increases gradually to 60.00Hz.

 

 

 

 

3

 

 

FR-DU04

CONTROL PANEL

 

 

 

 

 

Hz

 

 

 

 

 

A

 

 

 

 

 

V

 

 

 

MON

EXT

PU

 

 

 

 

REV

FWD

 

Deceleration

 

 

 

 

 

Slowly turn the potentiometer (frequency setting potentiometer) full

 

 

 

 

 

counterclockwise.

 

 

 

 

4

The frequency shown on the display decreases gradually to 0.00Hz.

 

 

 

 

The motor stops running.

 

FR-DU04

CONTROL PANEL

 

 

 

 

 

Hz

 

 

 

 

 

A

 

 

 

 

 

V

 

 

 

MON

EXT

PU

 

 

 

 

REV

FWD

 

Stop

Forward

 

 

 

 

Turn off the start switch (STF or STR).

 

 

 

 

rotation

Reverse

 

 

 

 

 

 

 

 

 

 

 

 

 

 

rotation

 

 

5

 

 

 

Stop

 

 

OFF

 

 

 

(2) External jog operation

Keep the start switch (STF or STR) on to perform operation, and switch it off to stop.

1)Set Pr. 15 "jog frequency" and Pr. 16 "jog acceleration/deceleration time".

2)Select the external operation mode.

3)Switch on the jog signal. Keep the start switch (STF or STR) on to perform operation.

Use any of Pr. 180 to Pr. 186 "input terminal function selection" to assign the terminal used for the jog signal.

57