PARAMETERS

<Setting>

Refer to the following list and set the parameters:

Setting

Signal

 

Functions

Relevant Parameters

Name

 

 

 

 

 

 

 

 

 

Pr. 4 to Pr. 6

0

RL

Pr. 59 = 0

Low-speed operation command

Pr. 24 to Pr. 27

 

 

Pr. 232 to Pr. 239

 

 

 

 

 

 

Pr. 59 = 1, 2*

Remote setting (setting clear)

Pr. 59

 

 

Pr. 59 = 0

Middle-speed operation command

Pr. 4 to Pr. 6, Pr. 24 to Pr. 27, Pr. 232 to

1

RM

Pr. 239

 

 

 

 

Pr. 59 = 1, 2*

Remote setting (deceleration)

Pr. 59

 

 

Pr. 59 = 0

High-speed operation command

Pr. 4 to Pr. 6, Pr. 24 to Pr. 27,

2

RH

Pr. 232 to Pr. 239

 

 

 

 

Pr. 59 = 1, 2*

Remote setting (acceleration)

Pr. 59

3

RT

Second function selection

Pr. 44 to Pr. 50

4

AU

Current input selection

 

Refer to page 10

5

JOG

Jog operation selection

 

Pr. 15, Pr. 16

6

CS

Automatic restart after instantaneous power failure selection

Pr. 57, Pr. 58, Pr. 162 to Pr. 165

 

 

External thermal relay input**

 

7

OH

The externally provided overheat protection thermal relay,

Refer to page 163

motor-embedded temperature relay or the like is operated to

 

 

 

 

 

stop the inverter.

 

 

10

X10

FR-HC connection (inverter operation enable)

Pr. 30, Pr. 70

11

X11

FR-HC connection (instantaneous power failure detection)

Pr. 30, Pr. 70

(Only when FR-A5NR option is fitted)

 

 

 

12

X12

PU operation external interlock

Pr. 79

13

X13

External DC dynamic braking start

Pr. 10 to Pr. 12

14

X14

PID control valid terminal

 

Pr. 128 to Pr. 134

16

X16

PU-external operation switch-over

Pr. 79

17

X17

Load pattern selection forward/reverse rotation boost

Pr. 14

24

X24

PID forward-reverse action switching function

Pr. 500 to Pr. 516

(NA, EC versions only)

 

 

 

 

 

9999

 

No function

 

 

*: When Pr. 59 = "1" or "2", the functions of the RL, RM, RH and RT signals change as listed above.

**: Operated when the relay contact "opens".

Note: 1. One function can be assigned to two or more terminals. In this case, the terminal inputs are OR’ed.

2.The speed command priorities are higher in order of jog, multi-speed setting (RH, RM, RL) and AU.

3.When HC connection (inverter operation enable signal) is not selected, the MRS terminal shares this function.

4.Use common terminals to assign the multi-speeds (7 speeds) and remote setting. They cannot be set individually.

(Common terminals are used since these functions are designed for speed setting and need not be set at the same time.)

5.When FR-HC connection inverter operation enable (X10) signal is not assigned, the MRS terminal shares this function.

6.When "7" is set in Pr. 79 and the PU operation external interlock (X12) signal is not assigned, the MRS signal acts as this function.

7.When the load pattern selection forward/reverse rotation boost (X17) signal is not assigned, the RT signal shares this function.