PROTECTIVE FUNCTIONS

 

 

 

 

 

 

 

 

 

 

 

Operation Panel

E.PUE

 

 

FR-PU04

 

PU Leave Out

 

 

Indication

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Name

Parameter unit disconnection

 

 

 

 

This function stops the inverter output if communication between the inverter

 

 

 

and PU is suspended, e.g. the operation panel or PU is disconnected, when "2",

 

 

 

"3", "16" or "17" was set in Pr. 75 "reset selection/disconnected PU detection/PU

 

 

Description

stop selection". This function stops the inverter output if the number of

 

 

successive communication errors is greater than the permissible number of

 

 

 

 

 

 

retries when the Pr. 121 value is "9999" for RS-485 communication from the PU

 

 

 

connector. This function stops the inverter output if communication is broken for

 

 

 

the time set in Pr. 122.

 

 

 

 

 

Check point

Check for loose fitting of the DU or PU.

 

 

 

Check the Pr. 75 setting.

 

 

 

 

 

 

 

 

 

 

 

Corrective action

Fit the DU and PU securely.

 

 

 

 

 

 

 

 

 

 

 

 

 

Operation Panel

E.RET

 

 

FR-PU04

 

Retry No Over

 

 

Indication

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Name

Retry count exceeded

 

 

 

 

 

Description

If operation cannot be resumed properly within the number of retries set, this

 

 

function stops the inverter output.

 

 

 

 

 

 

 

Check point

Find the cause of alarm occurrence.

 

 

 

Corrective action

Eliminate the cause of the error preceding this error indication.

 

 

 

 

 

 

 

 

 

 

 

 

Operation Panel

E.CPU

 

 

FR-PU04

 

CPU Fault

 

 

Indication

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Name

CPU error

 

 

 

 

 

 

If the arithmetic operation of the built-in CPU does not end within a

 

 

Description

predetermined period, the inverter self-determines it as an alarm and stops the

 

 

 

output.

 

 

 

 

 

Check point

 

 

 

 



 

 

 

Corrective action

Make connection securely.

 

 

 

 

 

 

 

 

 

 

Operation Panel

 

E. 6

 

 

FR-PU04

 

Fault 6

 

 

 

 

 

 

 

 

 

 

Indication

 

 

 

 

 

 

 

 

 

E. 7

 

 

 

 

Fault 7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Name

CPU error

 

 

 

 

 

Description

This function stops the inverter output if a communication error occurs in the

 

 

built-in CPU.

 

 

 

 

 

 

 

 

 

 

 

Check point

Check for a loose connector.

 

 

 

Corrective action

Contact your sales representative.

 

 