4.2.21 Second stall prevention (Pr. 48, Pr. 49)

Pr. 48 "second stall prevention operation current"

Pr. 49 "second stall prevention operation frequency"

Related parameters

Pr. 22 "stall prevention operation level" Pr. 23 "stall prevention operation level compensation factor at double

speed"

Pr. 66 "stall prevention operation level reduction starting frequency"

Pr. 154 "voltage reduction selection during stall prevention operation"

Pr. 180 to Pr. 186

(input terminal function selection)

#The stall prevention operation level can be changed within the range from 0Hz to the frequency set inPr. 49.

#The stall prevention operation level can be changed by switching the external input signal on-off.

Parameter

Factory

Setting Range

preventionStall

currentoperation

Number

Setting

 

 

 

 

 

48

120%

0 to 150%

 

 

49

0

0 to 120Hz, 9999

 

 

 

 

 

Pr.48

Acceleration

Deceleration/constant speed

Pr.49 Running frequency

<Setting>

Set the stall prevention operation level in Pr. 48.

Refer to the following list to set values in Pr. 49.

Pr. 49 Setting

 

Operation

0

Second stall prevention function is not activated.

0.01Hz to 120Hz

Second stall prevention function is activated according to the

frequency as shown above.

 

 

Second stall prevention function is activated according to the RT signal.

9999

RT signal ON

Stall level Pr. 48

 

RT signal OFF

Stall level Pr. 22

Note: 1. When Pr. 49 = "9999", setting "0" in Pr. 48 disables the stall prevention function when the RT signal switches on. When Pr. 49 "9999" and Pr. 48 = "0", the stall prevention operation level is 0% when the frequency is equal to or less than the value set in Pr. 49.

2.When the stall prevention operation level signal input function is selected (Pr. 22 = 9999), setting "9999" in Pr. 49 changes the stall prevention operation level from the value of the stall prevention operation level signal (terminal 1 input) to the value set in Pr. 48 when the RT signal switches on.

3.When the RT signal is on, the second functions such as second acceleration/deceleration time are also selected.

4.When terminal assignment is changed using Pr. 180 to Pr. 186, the other functions may be affected. Check the functions of the corresponding terminals before making setting.

4

CAUTION

Do not set a too small value to the second stall prevention operation current. Otherwise, torque generated will decrease.

Pr. 50 % Refer to Pr. 42.

85

Page 98