PARAMETERS

(5) Parameter setting

 

 

 

 

 

 

 

 

 

 

 

 

Parameter

Setting

Name

 

Description

 

Number

 

 

 

 

 

 

 

 

 

10

 

For heating, pressure control,

 

Deviation value

PID reverse

 

 

etc.

 

action

 

 

 

 

signal input

 

 

 

 

 

PID forward

 

11

 

For cooling, etc.

 

(terminal 1)

 

PID action

 

action

 

 

 

 

 

128

20

selection

For heating, pressure control,

 

Set point (terminal 2

PID reverse

 

etc.

 

or Pr. 133), Process

action

 

 

 

 

 

21

 

For cooling, etc.

 

value input, (terminal

PID forward

 

 

 

4)

action

 

 

 

 

 

 

30

Advanced PID control (NA, EC versions only)

 

 

 

 

31

 

 

 

 

 

 

 

 

 

 

 

 

If the proportional band is narrow (parameter setting is small), the

 

 

 

manipulated variable varies greatly with a slight change of the process value.

129

0.1 to 1000%

PID proportional

Hence, as the proportional band narrows, the response sensitivity (gain)

 

band

improves but the stability deteriorates, e.g. hunting occurs.

 

 

 

 

 

 

 

Gain K = 1/proportional band.

 

 

 

 

9999

 

No proportional control

 

 

 

 

Time only required for the integral (I) action to provide the same manipulated

130

0.1 to 3600 s

PID integral time

variable as that for the proportional (P) action. As the integral time

 

decreases, the set point is reached earlier but hunting occurs more easily.

 

 

 

 

9999

 

No integral control.

 

 

0 to 100%

 

Set the upper limit. If the feedback value exceeds the setting, the FUP signal

131

Upper limit

is output. (Process value of 4mA is equivalent to 0% and 20mA to 100%.)

 

 

9999

 

 

No function

 

 

 

 

Set the lower limit. If the feedback value falls below the setting, the FDN

132

0 to 100%

Lower limit

signal is output. (Process value of 4mA is equivalent to 0% and 20mA to

 

100%.)

 

 

 

 

 

 

 

 

 

 

9999

 

 

No function

 

 

 

PID action set

Only valid for the PU command in the PU operation or PU/external combined

 

 

mode.

 

 

 

133

0 to 100%

point for PU

 

 

 

For external operation, the voltage across 2-5 is the set point.

 

 

operation

 

 

(Pr. 902 value is equivalent to 0% and Pr. 903 value to 100%.)

 

 

 

 

 

 

Time only required for the differential (D) action to provide the same process

134

0.01 to 10.00 s

PID differential

value as that for the proportional (P) action. As the differential time

 

time

increases, greater response is made to the deviation change.

 

 

 

9999

 

No differential control.

 

(6) Adjustment procedure

Parameter setting

Terminal setting

Adjust the PID control parameters, Pr. 128 to Pr. 134

Set the I/O terminals for PID control. (Pr. 180 to Pr. 186, Pr. 190 to Pr.195) Pr. 128 = 10, 11, 20, 21

Switch X14 signal on.