STOP
RESET

PARAMETERS

<Function/operation changed by switching on-off the X12 (MRS) signal>

Operating Condition

 

 

Operation

 

 

 

Switching

Operation

 

X12 (MRS)

Mode

Operating Status

Parameter Write

to PU

Status

Signal

Operation

mode

(Note 4)

 

 

 

 

 

 

 

 

 

Mode

 

 

 

 

 

 

 

 

 

During stop

ON

OFF

 

During stop

Allowed

disallowed

Disallowed

 

(Note 3)

 

 

 

 

 

 

 

 

PU

 

 

 

External

If external operation

 

 

 

During

ON

OFF

frequency setting and start

Allowed

 

 

 

 

signal are entered,

disallowed

Disallowed

 

operation

(Note 3)

 

 

 

operation is performed in

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

that status.

 

 

 

 

During stop

OFF

ON

 

During stop

Disallowed

disallowed

Allowed

 

ON

OFF

 

Disallowed

disallowed

Disallowed

 

 

 

 

External

 

OFF

ON

External

During operation

Disallowed

disallowed

Disallowed

During

output stop

 

 

 

 

 

 

 

 

operation

ON

OFF

 

Output stop

Disallowed

disallowed

Disallowed

 

 

 

During operation

 

 

 

 

 

 

 

 

Note: 1. When the Pr. 79 setting is 7 and the PU operation interlock signal is OFF, network operation such as computer link cannot be used.

2.If the X12 (MRS) signal is on, the operation mode cannot be switched to the PU operation mode when the start signal (STF, STR) is on.

3.The operation mode switches to the external operation mode independently of whether the start signal (STF, STR) is on or off. Therefore, the motor is run in the external operation mode when

the X12 (MRS) signal is switched off with either of STF and STR on.

4. When an alarm occurs, the inverter can be reset by pressing the key of the operation panel.

5.When the MRS signal is used as the PU interlock signal, switching the MRS signal on and rewriting the Pr. 79 value to other than 7 in the PU operation mode causes the MRS signal to provide the ordinary MRS function (output stop). Also, as soon as 7 is set in Pr. 79, the MRS signal acts as a PU interlock signal.

6.When the MRS signal is used as the PU external interlock signal, the signal logic conforms to the Pr. 17 setting. When Pr. 17 = 2, read ON for OFF and OFF for ON in the above explanation.

(3) Operation mode external signal switching function

1) Preparation

Set "8" (switching to other than external operation mode) in Pr. 79. Using any of Pr. 180 to Pr. 186 (input 4 terminal function selection), allocate the terminal used to input the X16 (PU-external operation switching)

signal.

Refer to page 138 for Pr. 180 to Pr. 186 (input terminal function selection).

Note: When terminal assignment is changed using Pr. 180 to Pr. 186, the other functions may be affected. Check the functions of the corresponding terminals before making setting.

2)Function

When the X16 signal is switched on in the PU operation mode, the operation mode is forcibly changed to the external operation mode. When the X16 signal is switched off in the external operation mode, the operation mode is changed to the PU operation mode. When the X16 signal is switched off during network operation such as computer link, the operation mode is changed to the PU operation mode as soon as the switch-over command to the external operation mode is sent from the computer. Note that this switch-over may only be made while the inverter is at a stop and cannot be made during operation.

X16 Signal

Operation Mode

ON

External operation mode (cannot be changed to the PU operation mode)

OFF

PU operation mode (cannot be changed to the external operation mode)

107

Page 120
Image 120
Mitsumi electronic 55K, FR-F520-0.75K Operation mode external signal switching function, Operating Condition, X12 MRS