INSTALLATION AND WIRING

2.2.3 Wiring of the control circuit

(1) Wiring instructions

1)Terminals SD, SE and 5 are common to the I/O signals and isolated from each other. These common terminals must not be connected to each other or earthed.

2)Use shielded or twisted cables for connection to the control circuit terminals and run them away from the main and power circuits (including the 200V relay sequence circuit).

3)The frequency-input signals to the control circuit are micro currents. When contacts are required, use two or more parallel micro signal contacts or a twin contact to prevent a contact fault.

4)It is recommended to use the cables of 0.75mm2 gauge for connection to the control circuit terminals. If the cable gauge used is 1.25mm2 or more, the front cover may be lifted when there are many cables running or the cables are run improperly, resulting in an operation panel or parameter unit contact fault.

(2) Terminal block layout

Japanese and NA version

In the control circuit of the inverter, the terminals are arranged as shown below:

Terminal screw size: M3.5

Tightening torque: 1.2 Nm

A

 

B

 

C

 

PC

AM

10E

10

2

 

5

 

4

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

 

RL

 

RM

 

RH

RT

 

AU

STOP

MRS

RES

 

SD

 

FM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SE

 

RUN

SU

IPF

 

OL

FU

SD

STF

STR

JOG

CS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EC version

Terminal screw size: M3.5

Tightening torque: 1.2 Nm

A

 

B

C

 

SD

AM

10E

10

2

5

 

4

 

1

RL

RM

RH

 

RT

AU

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SE

 

RUN

 

SU

LPF

OL

FU

STOP

MRS

RES

 

PC

 

STF

STR

JOG

CS

 

FM

SD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

18

Page 29
Image 29
Mitsumi electronic FR-F520-0.75K, 55K Wiring of the control circuit, Terminal screw size M3.5 Tightening torque 1.2 N⋅ m