PARAMETERS

4.2.28 Retry function (Pr. 65, Pr. 67 to Pr. 69)

Pr. 65 "retry selection"

Pr. 67 "number of retries at alarm occurrence"

Pr. 68 "retry waiting time"

Pr. 69 "retry count display erasure"

When an alarm occurs, the retry function causes the inverter to automatically reset itself to make a restart and continue operation. You can select whether retry is made or not, alarms reset for retry, number of retries made, and waiting time.

Parameter

Factory

Setting Range

Number

Setting

 

65

0

0 to 5

67

0

0 to 10, 101 to 110

68

1 s

0 to 10 s

69

0

0

<Setting>

Use Pr. 65 to select alarms to be reset for retry.

Errors Reset for Retry

 

 

Setting

 

 

 

 

Display

0

1

2

3

4

5

 

 

E.OC1

#

#

 

#

#

#

 

 

E.OC2

#

#

 

#

#

 

 

 

E.OC3

#

#

 

#

#

#

 

 

E.OV1

#

 

#

#

#

 

 

 

E.OV2

#

 

#

#

#

 

 

 

E.OV3

#

 

#

#

#

 

 

 

E.THM

#

 

 

 

 

 

 

 

E.THT

#

 

 

 

 

 

 

 

E.IPF

#

 

 

 

#

 

 

 

E.UVT

#

 

 

 

#

 

 

 

E.FIN

 

 

 

 

 

 

 

 

E. GF

#

 

 

 

#

 

 

 

 

 

 

 

 

 

E. LF

 

 

 

 

 

 

 

4

E.OHT

#

 

 

 

 

 

 

 

 

 

 

 

 

 

E.OLT

#

 

 

 

#

 

 

 

E.OPT

#

 

 

 

#

 

 

 

E.OP1

#

 

 

 

#

 

 

 

E.OP2

#

 

 

 

#

 

 

 

E.OP3

#

 

 

 

#

 

 

 

E. PE

#

 

 

 

#

 

 

 

E.PUE

 

 

 

 

 

 

 

 

E.RET

 

 

 

 

 

 

 

 

E.CPU

 

 

 

 

 

 

 

 

E. 6

 

 

 

 

 

 

 

 

E. 7

 

 

 

 

 

 

 

 

E.P24

 

 

 

 

 

 

 

 

E.CTE

 

 

 

 

 

 

 

 

Note: # indicates the errors selected for retry.