Mitsumi electronic FR-F520-0.75K, 55K instruction manual Equivalent Capacity Limits

Models: FR-F520-0.75K 55K

1 217
Download 217 pages 2.41 Kb
Page 41
Image 41

INSTALLATION AND WIRING

Table 3 Equivalent Capacity Limits

Received Power Voltage

Reference Capacity

 

 

6.6kV

50kVA

 

 

22/33kV

300kVA

 

 

66kV or more

2000kVA

 

 

Table 4 Harmonic Content (Values at the fundamental current of 100%)

Reactor

5th

7th

11th

13th

17th

19th

23rd

25th

Not used

65

41

8.5

7.7

4.3

3.1

2.6

1.8

Used (AC side)

38

14.5

7.4

3.4

3.2

1.9

1.7

1.3

Used (DC side)

30

13

8.4

5.0

4.7

3.2

3.0

2.2

Used (AC, DC sides)

28

9.1

7.2

4.1

3.2

2.4

1.6

1.4

1) Calculation of equivalent capacity (P0) of harmonic generating equipment

The “equivalent capacity” is the capacity of a 6-pulse converter converted from the capacity of consumer’s harmonic generating equipment and is calculated with the following equation. If the sum of equivalent capacities is higher than the limit in Table 3, harmonics must be calculated with the following procedure:

P0 = Σ (Ki Pi) [kVA]

* Rated capacity: Determined by the

Ki: Conversion factor (refer to Table 2)

capacity of the applied motor and found

Pi: Rated capacity of harmonic generating equipment* [kVA]

in Table 5. It should be noted that the

i: Number indicating the conversion circuit type

rated capacity used here is used to

 

calculate generated harmonic amount

 

and is different from the power supply

capacity required for actual inverter

 

drive.

2

2) Calculation of outgoing harmonic current

 

Outgoing harmonic current = fundamental wave current (value converted from received power voltage)

 

operation ratio harmonic content

 

Operation ratio: Operation ratio = actual load factor operation time ratio during 30 minutes

Harmonic content: Found in Table 4.

Table 5 Rated Capacities and Outgoing Harmonic Currents for Inverter Drive

 

 

 

Fundamental

 

 

 

 

 

 

 

 

 

 

Applied

Rated Current [A]

Wave Current

Rated

 

Fundamental Wave Current Converted from 6.6kV

 

Motor

Converted

Capacity

 

 

(No reactor, 100% operation ratio)

 

 

 

 

 

 

 

 

(kW)

 

 

from 6.6kV

 

 

 

 

 

 

 

 

 

 

 

200V

400V

(mA)

(kVA)

5th

7th

 

11th

13th

17th

19th

23rd

25th

0.75

2.74 (Note)

1.37

83

0.97

53.95

34.03

 

7.055

6.391

3.569

2.573

2.158

1.494

1.5

5.50 (Note)

2.75

167

1.95

108.6

68.47

 

14.20

12.86

7.181

5.177

4.342

3.006

2.2

7.93 (Note)

3.96

240

2.81

156.0

98.40

 

20.40

18.48

10.32

7.440

6.240

4.320

3.7

13.0 (Note)

6.50

394

4.61

257.1

161.5

 

33.49

30.34

16.94

12.21

10.24

7.092

5.5

19.1

9.55

579

6.77

376.1

237.4

 

49.22

44.58

24.90

17.95

15.05

10.42

7.5

25.6

12.8

776

9.07

504.4

318.2

 

65.96

59.75

33.37

24.06

20.18

13.97

11

36.9

18.5

1121

13.1

728.7

459.6

 

95.29

86.32

48.20

34.75

29.15

20.18

15

49.8

24.9

1509

17.6

980.9

618.7

 

128.3

116.2

64.89

46.78

39.24

27.16

18.5

61.4

30.7

1860

21.8

1209

762.6

 

158.1

143.2

79.98

57.66

48.36

33.48

22

73.1

36.6

2220

25.9

1443

910.2

 

188.7

170.9

95.46

68.82

57.72

39.96

30

98.0

49.0

2970

34.7

1931

1218

 

252.5

228.7

127.7

92.07

77.22

53.46

37

121

60.4

3660

42.8

2379

1501

 

311.1

281.8

157.4

113.5

95.16

65.88

45

147

73.5

4450

52.1

2893

1825

 

378.3

342.7

191.4

138.0

115.7

80.10

55

180

89.9

5450

63.7

3543

2235

 

463.3

419.7

234.4

169.0

141.7

98.10

Note: When a motor of 3.7kW or less capacity is driven by a transistorized inverter of more than 3.7kW. For example, when a 3.7kW or less motor is driven by a 5.5kW transistorized inverter, the transistorized inverter is not the target of the household appliances/general-purpose products guideline, but because they must be included in the calculation of the harmonic current of the guideline, the fundamental wave input currents are indicated.

3)Harmonic suppression technique requirement

If the outgoing harmonic current is higher than; maximum value per 1kW (contract power) contract power, a harmonic suppression technique is required.

30

Page 41
Image 41
Mitsumi electronic FR-F520-0.75K Equivalent Capacity Limits, Harmonic Content Values at the fundamental current of 100%