Mitsumi electronic 55K, FR-F520-0.75K instruction manual Applied motor Pr, Pr applied motor, Motor

Models: FR-F520-0.75K 55K

1 217
Download 217 pages 2.41 Kb
Page 110
Image 110

PARAMETERS

4.2.29 Applied motor (Pr. 71)

Pr. 71 "applied motor"

Related parameters

Pr. 0 "torque boost"

Pr. 12 "DC injection brake voltage" Pr. 19 "base frequency voltage" Pr. 60 "intelligent mode selection" Pr. 100 to Pr. 109

(V/F frequency/voltage)

Set the motor used.

Parameter

Factory

Setting Range

Number

Setting

 

71

0

0, 1, 2

<Setting>

Refer to the following list and set this parameter according to the motor used.

Pr. 71

 

Motor

Thermal Characteristics of Electronic Overcurrent Protection

 

Constant

Setting

Standard

 

Torque

 

 

 

0

Thermal characteristics matching a standard motor

$

 

1

Thermal characteristics matching the Mitsubishi constant-torque motor

 

$

2

Thermal characteristics matching a standard motor

$

 

5-point flexible V/F characteristics

 

 

 

 

For the 5.5K and 7.5K, the Pr. 0 and Pr. 12 settings are automatically changed depending on the Pr. 71 setting.

Pr. 71

0, 2

1

Pr. 0

3%

2%

Pr. 12

4%

2%

Note: 1. When "9999" is set in Pr. 19, "2" cannot be set in Pr. 71. To set "2" in Pr. 71, set the appropriate value (other than "9999") in Pr. 19.

2.When "2" is set in Pr. 71, Pr. 100 to Pr. 109 are displayed on the parameter unit (FR-PU04). In other settings, if any of Pr. 100 to Pr. 109 settings is changed, the new setting is not displayed in the "Default parameter list" and "Set parameter list".

CAUTION

Set this parameter correctly according to the motor used.

Incorrect setting may cause the motor to overheat and burn.

4

97

Page 110