Mitsubishi Electronics FR-S500 Communication Parameters, Function Parameter list, Parameter List

Models: FR-S500

1 196
Download 196 pages 9.03 Kb
Page 69
Image 69
 Communication Parameters

Function (Parameter) list

0: As set in Pr. 79. Communication Parameters

 

 

 

 

 

Minimum

 

 

Cus-

Func

Parame-

Indica-

Name

Setting Range

Setting

Factory

Refer

tomer

tion

ter

tion

 

 

Incre-

Setting

To:

Setting

 

 

 

 

 

ments

 

 

 

 

 

 

Communication

0 to 31: Specify

 

 

 

 

 

n1 (331)

 

the station

1

0

132

 

 

 

station number

number of the

 

 

 

 

 

 

 

 

 

 

 

 

inverter.

 

 

 

 

 

n2 (332)

 

Communication

48: 4800bps,

1

192

132

 

 

 

speed

96: 9600bps,

 

 

 

 

192: 19200bps

 

 

 

 

 

 

 

 

 

 

 

 

 

n3 (333)

 

Stop bit length

0, 1: (Data length 8),

1

1

132

 

 

 

10, 11: (Data

 

 

 

 

 

length 7)

 

 

 

 

 

 

 

Parity check

0: Absent,

 

 

 

 

 

n4 (334)

 

1: With odd parity

1

2

132

 

 

 

presence/

check,

 

 

 

 

absence

2: With even

 

 

 

 

 

 

 

 

parity check

 

 

 

 

 

 

 

Number of

 

 

 

 

 

 

n5 (335)

 

communication

0 to 10, - - -

1

1

132

 

 

 

 

retries

 

 

 

 

 

 

 

 

Communication

 

 

 

 

 

Parameters

n6 (336)

 

check time

0 to 999s, - - -

0.1s

- - -

132

 

 

 

interval

0: Command

 

 

 

 

 

 

 

 

 

 

 

 

 

n7 (337)

 

Waiting time

0 to 150ms, - - -

1

- - -

132

 

 

 

setting

 

 

 

 

 

 

 

 

 

Communication

 

 

 

source is

 

 

 

 

 

 

Operation

computer,

1

0

147

 

 

n8 (338)

 

1: Command

 

 

 

command source

 

 

 

 

 

source is

 

 

 

 

 

 

 

 

external

 

 

 

 

 

 

 

 

terminal

 

 

 

 

 

 

 

 

0: Command

 

 

 

 

 

 

 

 

sourse is

 

 

 

 

 

 

 

Speed command

computer,

1

0

147

 

 

n9 (339)

 

1: Command

 

 

 

 

source

source is

 

 

 

 

 

 

 

 

external

 

 

 

 

 

 

 

 

terminal

 

 

 

 

 

 

 

 

0: As set in Pr. 79.

 

 

 

 

 

n10

 

Link startup

1: Started in

1

0

148

 

 

(340)

 

mode selection

computer link

 

 

 

 

 

 

 

 

 

 

 

operation mode.

 

 

 

 

 

 

 

 

0: Without CR/LF,

 

 

 

 

 

n11

 

CR/LF selection

1: With CR,

1

1

132

 

 

(341)

 

 

without LF

 

 

 

 

 

 

 

 

2: With CR/LF

 

 

 

 

 

 

 

 

0: Write to RAM

 

 

 

 

 

n12

 

E2PROM write

and E2PROM

1

0

150

 

 

(342)

 

selection

1: Write to RAM

 

 

 

 

 

 

 

 

 

 

 

only

 

 

 

 

Parameter List

2

FUNCTIONS

59

Page 69
Image 69