Errors (Alarms)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Operation Panel Indication

PS

 

 

 

 

FR-PU04

 

PS

 

 

 

 

 

 

 

Name

PU stop

 

 

 

 

 

 

Pr. 75 "reset selection/PU stop selection" had been set and a stop

Description

was made by pressing the

RESETSTOP of the operation panel or

 

parameter unit (FR-PU04) during operation in the external

 

operation mode.

 

 

 

 

Check point

Check for a stop made by pressing the RESETSTOP

of the operation

 

panel during external operation.

 

Corrective action

Refer to page 105.

 

 

 

 

 

 

 

 

 

 

Operation Panel Indication

UV

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Name

Undervoltage

 

 

 

 

 

 

If the power supply voltage of the inverter reduces, the control

 

circuit will not operate properly and will result in decreased motor

Description

torque or increased heat generation. To prevent this, if the power

supply voltage reduces below about 115VAC (about 230VAC for

 

the three-phase 400V power input series, about 58VAC for the

 

single-phase 100V power input series), this function stops the

 

inverter output.

 

 

 

 

Check point

• Check for a start of large-capacity motor.

 

• Check that the power supply capacity is as indicated in the

 

specifications (Refer to page 170.).

 

Corrective action

Check the power supply system equipment such as the power

supply.

 

 

 

 

 

 

 

 

 

PROTECTIVE FUNCTIONS

3

163