Mitsubishi Electronics FR-S500 instruction manual Common specifications, Specification list

Models: FR-S500

1 196
Download 196 pages 9.03 Kb
Page 183
Image 183
4.1.2Common specifications

Specification list

4.1.2Common specifications

Control specifications

Control system

Output frequency range

Frequency setting resolution

Frequency accuracy

Starting torque

Acceleration/deceleration time setting

Braking torque

Regeneration

(*2)

 

DC injection

 

Frequency

brake

 

Analog input

 

setting

Digital input

 

signal

 

Start signal

STF, STR

 

Alarm reset

 

 

 

signals

Multi-speed selection

Second function selection

Input

 

 

 

Output stop

 

Current input selection

External thermal relay input

Jog signal

PID control valid

PU operation /external operation switchover

Selectable between Soft-PWM control and high carrier frequency PWM control, V/F control or automatic torque boost control are selectable.

0.5to 120Hz (starting frequency variable between 0 and 60Hz)

5VDC input: 1/500 of max. set frequency, 10VDC,

4 to 20mADC input: 1/1000 of max. set frequency

Digital input: 0.1Hz (less than 100Hz), 1Hz (100Hz or higher)

Analog input: Within ±1% of max. output frequency (25°C±10°C)

Digital input: Within ±0.5% of set output frequency (when set by the setting dial)

150% (at 5Hz) during automatic torque boost control

0, 0.1 to 999s (acceleration and deceleration can be set individually), linear or S-pattern acceleration/deceleration mode can be selected.

0.1K, 0.2K ... 150%, 0.4K, 0.75K ... 100%, 1.5K ... 50%, 2.2K, 3.7K ... 20%

Operation frequency (0 to 120Hz), operation time (0 to 10s), operation voltage (0 to 15%)

0 to 5VDC, 0 to 10VDC, 4 to 20mA

Entered from operation panel

Forward and reverse rotation, start signal automatic self-holding input (3-wire input) can be selected.

Used to reset alarm output provided when protective function is activated.

Up to 15 speeds can be selected. (Each speed can be set between 0 and 120Hz, running speed can be changed during operation from the operation panel.)

Used to select second functions (acceleration

Use

time, deceleration time, torque boost, base

frequency, electronic thermal relay function).

Pr. 60 to

Instantaneous shut-off of inverter output

Pr. 63 for

(frequency, voltage)

selection

Used to select frequency setting signal 4 to 20

 

mA (terminal 4).

 

Thermal relay contact input for use when the inverter is stopped by the external thermal relay.

Jog operation mode selection Selection for exercising PID control

Used to switch between PU operation and external operation from outside the inverter.

SPECIFICATIONS