(2)Operation mode switching by external signal

Operation selection function parameters

REMARKS

•If the MRS signal is on, the operation mode cannot be switched to the PU operation mode when the start signal (STF, STR) is on.

*1. The operation mode switches to the external operation mode independently of whether the start signal (STF, STR) is on or off.

Therefore, the motor is run in the external operation mode when the MRS signal is switched off with either of STF and STR on.

*2. Switching the MRS signal on and rewriting the Pr. 79 value to other than "7" in the PU operation mode causes the MRS signal to act as the ordinary MRS function (output stop). Also as soon as "7" is set in Pr. 79, the signal acts as the PU interlock signal.

(2)Operation mode switching by external signal

1)Preparation

Set "8" (switching to other than external operation mode) in Pr. 79.

Use any of Pr. 60 to Pr. 63 (input terminal function selection) to set the terminal used for X16 signal input.

CAUTION

When terminal assignment is changed using Pr. 60 to Pr. 63, the other functions may be affected.

Check the functions of the corresponding terminals before making settings. For details refer to page 98.

2)Function

This switching is enabled during an inverter stop only and cannot be achieved during operation.

X16 Signal

Operation Mode

ON

External operation mode (cannot be changed to the PU operation mode)

OFF

PU operation mode (cannot be changed to the external operation mode)

1)Preparation to Set "8" (switching to other than external operation mode) in Pr. 79.2)Function Refer to  to  Refer to  to  (page 66). to Manual background (page 66).