Mitsubishi Electronics FR-S500 Reverse rotation prevention selection Pr, Setting

Models: FR-S500

1 196
Download 196 pages 9.03 Kb
Page 119
Image 119
2.10.8 Reverse rotation prevention selection (Pr. 78 )

Operation selection function parameters

2.10.8 Reverse rotation prevention selection (Pr. 78 2.10.9Operation mode selection (Pr. 79 ))

This function can prevent reverse rotation faults resulting from the incorrect input of the start signal.

POINT

Used for a machine which runs only in one direction, e.g. fan, pump.

(The setting of this function is valid for the combined, PU, external and communication operations.)

Parameter

Name

Factory

Setting

Remarks

Setting

Range

 

 

 

78

Reverse rotation

0

0, 1, 2

Setting is enabled when Pr. 30 = "1"

prevention selection

 

 

 

 

<Setting>

Pr. 78 Setting

Function

0Both forward and reverse rotations allowed

1Reverse rotation disallowed

2Forward rotation disallowed

2.10.9Operation mode selection (Pr. 79 Manual background)

Used to select the operation mode of the inverter.

The inverter can be run from the operation panel or parameter unit (PU operation), with external signals (external operation), or by combination of PU operation and external operation (external/PU combined operation).

The inverter is placed in the external operation mode at power on (factory setting).

Parameter

Name

Factory Setting

Setting Range

79

Operation mode selection

0

0 to 4, 7, 8

2

FUNCTIONS

109

Page 119
Image 119
Mitsubishi Electronics FR-S500 Reverse rotation prevention selection Pr, Operation mode selection Pr, Setting