Connection to the Stand-Alone Option

1.6.3Connection of the power regeneration common converter (FR-CV)

When connecting the FR-CV type power regeneration common converter, connect the inverter terminals (P, N) and FR-CV type power regeneration common converter terminals as shown below so that their signals match with each other.

NFB MC1

Three-phase AC power supply

 

 

 

 

R

 

 

 

 

 

S

(Caution 2)

 

 

 

 

T

 

Dedicated stand-alone

FR-CV power regenerative

Inverter

reactor (FR-CVL)

common converter

 

 

 

R/L11

R2/L12

(Caution 3)

 

 

 

R2/L1

 

(Caution 5)

 

S/L21

S2/L22

 

 

S2/L2

P/L+

P

 

T/L31

T2/L32

 

T2/L3

N/L-

N

(Caution 7)

 

 

 

 

(Caution 6)

P24

PC

 

 

 

R/L11

SD

SD (Caution 1)

 

 

S/L21

 

 

RDYA

 

 

 

 

T/MC1

 

 

 

 

 

 

 

 

 

 

RDYB

MRS (Caution 4)

 

 

 

RSO

RES (Caution 4)

 

 

 

SE

 

 

U

V IM W

CAUTION

1.Use sink logic (factory setting) when the FR-CV is connected. The FR-CV cannot be connected when source logic is selected.

2.The power input terminals R, S, T must be open. Incorrect connection will damage the inverter. Opposite polarity of terminals N, P will damage the inverter.

3.The voltage phases of terminals R/L11, S/L21, T/MC1 and terminals R2/L1, S2/L2, T2/L3 must be matched before connection.

4.Use Pr. 60 to Pr. 63 (input terminal function selection) to assign the terminals used for the RES and MRS signals.

5.Do not insert NFB between terminals P-N (P/L+ - P, N/L- N)

6.Make sure to connect the terminal R/L11, S/L21, T/MC1 to the power supply. Running the inverter without connecting the terminals will damage the power regeneration common converter.

7.The N terminal is not provided for the FR-S520E-0.1K to 0.75K.