The terminal functions change with input terminal function selection (Pr. 60 to Pr.63). (*3)

Standardconnection diagramand terminal specifications

(2) Control circuit

Symbol

Terminal Name

 

 

 

STF

Forward rotation

 

 

 

 

start

input

 

 

STR

Reverse rotation

Contact

 

 

 

start

 

 

RH

Multi-speed

 

 

 

RM

 

 

 

RL

selection

 

 

 

 

 

 

 

SD

Contact input

 

 

 

(*1)

common (sink)

 

 

 

 

External

 

 

 

 

transistor

 

PC

common, 24VDC

 

(*1)

power supply,

 

 

 

 

contact input

 

 

 

 

common (source)

10Frequency setting power supply

signalsInput setting

2

Frequency setting

 

 

(voltage signal)

 

 

Frequency

4

Frequency setting

 

 

(current signal)

 

 

5Frequency setting input common

Definition

Turn on the STF signal to

When the STF and STR

signals are turned on

start forward rotation and

simultaneously, the stop

turn it off to stop.

command is given.

 

Turn on the STR signal to start reverse rotation and turn it off to stop.

Turn on the RH, RM and RL signals in appropriate combinations to select multiple speeds.

The priorities of the speed commands are in order of jog, multi-speed setting (RH, RM, RL, REX) and AU.

Common to the contact input terminals (STF, STR, RH, RM, RL). (*6)

When connecting the transistor output (open collector output), such as a programmable controller (PLC), connect the positive external power supply for transistor output to this terminal to prevent a malfunction caused by undesirable currents.

This terminal can be used as a 24VDC, 0.1A power output across terminals PC-SD.

When source logic has been selected, this terminal serves as a contact input common.

5VDC, Permissible load current 10mA.

Inputting 0 to 5VDC (or 0 to 10V) provides the maximum output frequency at 5V (10V) and makes input and output proportional. Switch between 5V and 10V using Pr. 73 "0-5V, 0-10V selection". Input resistance 10kΩ. Maximum permissible input voltage 20V

Input 4 to 20mADC. It is factory set at 0Hz for 4mA and at 60Hz for 20mA.

Maximum permissible input current 30mA. Input resistance approximately 250Ω.

Turn ON signal AU for current input.

Turning the AU signal on makes voltage input invalid. Use any of Pr. 60 to Pr. 63 (input terminal function selection) to set the AU signal.

Common terminal for the frequency setting signals (terminal 2, 4) and indicator connection (terminal AM). (*6)

4