Hitachi J300U Series instruction manual Select the motor capacity which is the most approxi

Models: J300U Series

1 145
Download 145 pages 53.04 Kb
Page 135
Image 135

No.

Operation conditions

Phenomena

Improvements

NOTE: The setting methods shown below

 

Display, etc.

 

 

apply to DOP and DRW operations.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

Parallel motor operation

Operation cannot be started at high

1. When sensor-less vector control is selected

 

 

 

 

 

torque, since the inverter does not

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Function mode

 

 

 

 

 

 

 

 

know the load sharing of the

 

 

 

 

 

 

 

 

F-04

 

 

 

 

 

 

 

 

 

 

motors.

 

 

 

 

 

 

12.3 Function mode

 

 

 

CONTROL SLV VC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F-04 (P.12-5)

 

 

 

 

 

 

 

 

Reset to V/f control.

 

 

 

 

 

 

 

 

A

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Select the motor capacity which is the most approxi-

The sensor-less vector

 

 

 

mate to the total capacity of the motors used.

 

 

 

control is not applicable

 

 

 

(For example, 7.5 kW, 5.5 kW, and 3.7 kW.)

to multi-motor parallel

Function mode

operation.

A-23

Total capacity of the motors: 7.5 + 5.5 + 3.7 = 16.7kW

F-05

AUX K 022.00 kW 015.00 kW

Select the most approximate value to the total capacity.

If two or more motors are changed in operation, select the most approximate value to the motor capacity.

Example 1: One 5.5 kW motor is used

F-05

AUX K 022.00 kW 005.50 kW

Select the most approximate value.

Example 2: One 5.5 kW motor is changed into parallel operation of four 5.5 kW motors

Total capacity of the motors: 5.5 × 4 = 22.0 kW

F-04

AUX K 005.50 kW 022.00 kW

Select the most approximate value.

Page 135
Image 135
Hitachi J300U Series Select the motor capacity which is the most approxi, Mate to the total capacity of the motors used