Display

(Function mode 1)

(Function mode 2)

 

 

Setting, change

 

 

 

 

 

 

 

 

Function

Function

Initialization display

 

Initialization

Setting contents

sequence

 

contents

No.

name

contents

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

F-23

Electronic

E-THM A1

8.5A

 

Rated capacity of

0 to 600.0 A

 

 

Electronic

thermal

 

 

 

each inverter

 

 

 

thermal

characteristic

 

 

 

 

 

 

 

(NOTE 2)

free setting

 

 

 

 

 

 

 

 

current (1)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Electronic

E-THM F1

0000 Hz

 

Rated capacity of

0 to 400 Hz

 

 

 

thermal

 

 

 

each inverter

 

 

 

 

characteristic

 

 

 

 

 

 

 

 

free setting

 

 

 

 

 

 

 

 

frequency(1)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Electronic

E-THM A2

8.5A

 

Rated capacity of

0 to 600.0 A

 

 

 

thermal

 

 

 

each inverter

 

 

 

 

characteristic

 

 

 

 

 

 

 

 

free setting

 

 

 

 

 

 

 

 

current (2)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Electronic

E-THM F2

5 Hz

 

Rated capacity of

0 to 400 Hz

 

 

 

thermal

 

 

 

each inverter

 

 

 

 

characteristic

 

 

 

 

 

 

 

 

free setting

 

 

 

 

 

 

 

 

frequency(2)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Electronic

E-THM A3

13.0 A

 

Rated capacity of

0 to 600.0 A

 

 

 

thermal

 

 

 

each inverter

 

 

 

 

characteristic

 

 

 

 

 

 

 

 

free setting

 

 

 

 

 

 

 

 

current (3)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Electronic

E-THM F3

73 Hz

 

Rated capacity of

0 to 400 Hz

 

 

 

thermal

 

 

 

each inverter

 

 

 

 

characteristic

 

 

 

 

 

 

 

 

free setting

 

 

 

 

 

 

 

 

frequency(3)

 

 

 

 

 

 

 

 

 

 

 

 

 

17

F-24

Overload

OLOAD LEVEL125%

125%

50 to 150%

Under the sensorless vector

 

Overload

restriction

 

 

 

 

 

control, an overload is detected

 

restriction

level setting

 

 

 

 

 

from both the overload restric-

 

 

 

 

 

 

 

 

tion and torque limiter.

 

 

 

 

 

 

 

 

 

Overload

OLOAD CONST01.0

1.0

0.3 to 31.0

When the setting is 31.0 in SLV

 

 

restriction

 

 

 

 

 

or V2 control mode, the

 

 

constant

 

 

 

 

 

overload restriction has no

 

 

setting

 

 

 

 

 

effect.

 

 

 

 

 

 

 

 

 

 

Valid

OLOAD ACC ON

 

ON

ON: Valid for

Even if the function is set to

 

 

selection

 

 

 

 

acceleration

OFF, the overload restriction is

 

 

for overload

 

 

 

 

Keep the

invalid only for the first

 

 

restriction

 

 

 

 

function ON

acceleration when the forward

 

 

acceleration

 

 

 

 

for operation.

and reverse run command is

 

 

 

 

 

 

 

 

turned on.

 

 

 

 

 

 

 

 

 

18

F-25

Software

S-LOCK

MD1

 

MD1

MD0/MD1

MD0, MD1: Terminal software

 

 

lock

 

 

 

 

MD2/MD3

lock (SFT)

 

 

selection

 

 

 

 

 

MD2, MD3: Software lock

 

 

 

 

 

 

 

 

(NOTE 1)

 

 

 

 

 

 

 

 

 

NOTE 1: When MD0 is set and the input terminal SFT is turned ON, the data of all functions is locked. When MD2 is set (stored), the data of all the functions is locked. During locking, no data can be changed. MD1, MD3 can set only the output frequency.

NOTE 2: Electronic thermal characteristic free setting current and frequency depends on the inverter rating.

12-9

Page 100