(2)Extension function mode

Each function name and settable range to the extension function mode are shown below.

Set the extension function code to be changed by .

Display

 

 

 

Screen display

 

Settable

 

Set

Externsion function name

 

 

 

 

for

Remarks

order

Code

Settable

Setting range

Initial value

2nd

value

 

 

display

during

function

 

 

 

 

running

 

 

 

 

 

1

Control method setting

A 0

Ñ

0-5

0

 

 

2

Motor capacity setting

A 1

Ñ

3.7 to 160

 

NOTE 1

 

3

Motor poles setting

A 2

Ñ

2/4/6/8

4

 

 

4

Speed control response constant setting

A 3

Ñ

0.00-9.99/10.0-99.9/100

2.00

 

 

5

Start frequency adjustment

A 4

Ñ

0.10-9.99

0.50

Ñ

 

 

6

Maximum frequency limiter setting

A 5

Ñ

0-120 (400)

0

Ñ

 

 

7

Minimum frequency limiter setting

A 6

Ñ

0-120 (400)

0

Ñ

 

 

8

Jump frequency setting 1

A 7

Ñ

0-400

0

Ñ

 

 

9

Jump frequency setting 2

A 8

Ñ

0-400

0

Ñ

 

 

10

Jump frequency setting 3

A 9

Ñ

0-400

0

Ñ

 

 

11

Carrier frequency setting

A10

Ñ

2.0-16.0

(16.0)

Ñ

See 7-18

 

12

Frequency command sampling frequency

A11

Ñ

1-8

8

Ñ

 

 

13

Multispeed first speed setting

A12

Ñ

0-120 (400)

0

Ñ

 

 

14

Multispeed second speed setting

A13

Ñ

0-120 (400)

0

Ñ

 

 

15

Multispeed third speed setting

A14

Ñ

0-120 (400)

0

Ñ

 

 

16

Electronic thermal level adjustment

A23

Ñ

20-120

100

 

 

17

Electronic thermal characteristic selection

A24

Ñ

0-2

1

 

 

18

Motor pole number setting for motor speed monitor

A25

Ñ

2 to 48

4

Ñ

 

 

19

External frequency setting start

A26

Ñ

0-120 (400)

0

Ñ

 

 

20

External frequency setting end

A27

Ñ

0-120 (400)

0

Ñ

 

 

21

Instantaneous restart selection

A34

Ñ

0-3

0

Ñ

 

 

22

Dynamic braking usage ratio

A38

Ñ

0.0-99.9/100

(1.5)

Ñ

See 7-21

 

23

Optional arrival frequency for acceleration

A39

Ñ

0-400

0

Ñ

 

 

24

Optional arrival frequency for deceleration

A40

Ñ

0-400

0

Ñ

 

 

25

Monitor signal selection

A44

Ñ

0-3

0

Ñ

 

 

26

Frequency converted value setting

A47

Ñ

0.0-99.9

1.0

Ñ

 

 

27

Analog input selection

A48

Ñ

0-1

1

Ñ

 

 

28

Frequency arrival signal output method

A49

Ñ

0-2

0

Ñ

 

 

29

Restarting after FRS signal selection

A54

Ñ

0-1

1

Ñ

 

 

30

Reduced voltage soft start setting

A58

Ñ

0-6

6

Ñ

 

 

31

Running mode selection

A59

Ñ

0-2

0

Ñ

 

 

32

Jogging freguency setting

A61

Ñ

0-9.99

1.00

Ñ

Frequencies below

 

 

 

 

 

 

 

 

the start frequency

 

 

 

 

 

 

 

 

cannot be set.

 

33

Base frequency setting

A62

Ñ

30-120 (400)

60

 

 

34

Maximum frequency setting

A63

Ñ

30-120 (400)

60

 

 

35

Maximum frequency selection

A64

Ñ

120/400

120

Ñ

 

 

36

Frequency command/output frequency adjust (O-L terminal)

A80

Ñ

0-255

Ñ

Ñ

NOTE 2

 

37

Frequency command/output frequency adjust (OI-L terminal)

A81

Ñ

0-255

Ñ

Ñ

NOTE 2

 

38

Selection of reset terminal performance

A86

Ñ

0, 1

0

Ñ

 

 

39

P gain setting of PID funciton

A90

Ñ

0.1-0.5

1.0

Ñ

 

 

40

I gain setting of PID funciton

A91

Ñ

0.0-15.0

1.0

Ñ

 

 

41

D gain settingof PID function

A92

Ñ

0.0-100

0.0

Ñ

 

 

42

Selection of PID funciton

A94

Ñ

0-4

0

Ñ

 

 

43

Setting method of PID reference value

A95

Ñ

0, 1

0

Ñ

 

 

44

Setting of PID reference value

A96

Ñ

0.00-200

0.00

Ñ

 

 

45

Auto tuning setitng

A97

Ñ

0-2

0

Ñ

 

 

46

Motor data selection

A98

Ñ

0-2

0

 

 

47

Ro-To option selection

A99

Ñ

0-1

0

Ñ

 

 

48

Input terminal setting 1

C 0

Ñ

0-3, 5-9, 11-16, 18-28

18

Ñ

 

 

49

Input terminal setting 2

C 1

Ñ

0-3, 5-9, 11-16, 18-28

16

Ñ

 

 

50

Input terminal setting 3

C 2

Ñ

0-3, 5-9, 11-16, 18-28

5

Ñ

 

 

51

Input terminal setting 4

C 3

Ñ

0-3, 5-9, 11-16, 18-28

11

Ñ

 

 

52

Input terminal setting 5

C 4

Ñ

0-3, 5-9, 11-16, 18-28

9

Ñ

 

 

53

Input terminal setting 6

C 5

Ñ

0-3, 5-9, 11-16, 18-28

13

Ñ

 

 

54

Input terminal setting 7

C 6

Ñ

0-3, 5-9, 11-16, 18-28

1

Ñ

 

 

55

Input terminal setting 8

C 7

Ñ

0-3, 5-9, 11-16, 18-28

0

Ñ

 

 

56

Output terminal setting 11

C10

Ñ

0-2

0

Ñ

 

 

57

Output terminal setting 12

C11

Ñ

0-2

1

Ñ

 

 

58

Input terminal a and b contact setting

C20

Ñ

00-FF

00

Ñ

 

 

59

Output terminal a and b contact setting

C21

Ñ

00-07

04

Ñ

 

 

NOTE 1: The most applicable motor capacity of the inverter is set.

NOTE 2: The initial setting of each inverter is adjusted when shipping from the works.

7-6

Page 46
Image 46
Hitachi J300U Series instruction manual Screen display