10-3

Daily Inspection and Periodic Inspection (1/3)

Inspection

Inspection item

Inspection content

Inspection cycle

Inspection method

Criteria

Standard

Instruments

 

 

replacement

location

 

 

 

 

Daily

Periodic

 

 

period

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Overall

Ambient

Check ambient temperature,

 

 

 

Ambient temperature

__

Thermometer

 

environment

humidity, dust, corrosive

 

 

 

between -10 to +50˚C;

 

 

 

 

gases, oil mist, etc.

 

 

 

no icing.

 

 

 

 

 

 

 

 

Ambient humidity 20 to

 

 

 

 

 

 

 

 

90%; no dew condensation.

 

 

 

Devices overall

Check for abnormal

 

 

Visual and aural

 

 

Hygrometer

 

 

vibrations and noise.

 

 

inspection.

 

 

 

 

Power supply

Check the input line voltage.

 

 

Measure the voltage

No abnormalities.

 

Tester

 

voltage

 

 

 

between inverter

200 to 220 V, 50 Hz

 

 

 

 

 

 

 

terminals R(L1),

200 to 230 V, 60 Hz

 

 

 

 

 

 

 

S(L2) and T(L3).

380 to 415 V, 50 Hz

 

 

 

 

 

 

 

 

400 to 460 V, 60 Hz

 

 

Main

Overall

(1) Insulation resistance test

 

 

(1) Increase tighting

No abnormalities in (1) and

__

500 V class

circuit

 

(between main circuit

 

 

Making a check

(2).

 

Megohm meter

 

 

terminals and grounding

 

 

on the terque is

Tightening torque (kgf.cm)

 

 

 

 

terminal)

 

 

needed for the

 

 

 

 

 

 

 

increase tighten-

• M3: 8 - 10

 

 

 

 

(2) Check installation for

 

 

ing of the modules

• M4: 12 - 15

 

 

 

 

looseness.

 

 

such as a power

• M5: 20 - 25

 

 

 

 

 

 

 

module, diode

• M6: 25 - 30

 

 

 

 

(3) Check for evidence of

 

 

module. Do not

• M8: 100 - 135

 

 

 

 

overheating in the various

 

 

execute increse

• M10: 150 - 200

 

 

 

 

components.

 

 

tightening with

Tightening torque for IPM

 

 

 

 

 

 

 

no torque gauge

 

 

 

 

(4) Clean.

 

 

prepared.

and Diode modules

 

 

 

 

 

 

 

 

(kgf.cm)

 

 

 

 

 

 

 

(2) Tighten.

• M4: 10-15

 

 

 

 

 

 

 

• M5: 15-20

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(3) Visual

• M6: 20-25

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

inspection.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Page 84
Image 84
Hitachi J300U Series 10-3, Daily Inspection and Periodic Inspection 1/3, Instruments, Location Daily Periodic