Appendix 2 Instantaneous Power Failure Restart and Commercial Power Source Switching

1. Instantaneous power failure restart

[Function Outline]

This function allows an inverter operation to be selected according to the subject system as follows when an instantaneous power failure occurs.

Retry mode: When FTP/RST/ZST is set at IPS POWR

Alarm mode: When ALM is set at IPS POWR

• f matching:

The rotation speed and the phase are detected while the motor is on a free

 

running to restart the operation accordingly.

WARNING

lWhen the inverter stops due to a trip with retry mode selected, the motor restarts suddenly. Stand clear of the machine. Otherwise, you may be injured. (Design the machine in such a way that persons are protected against a restart of the machine.)

[Setting Method]

 

 

 

 

 

 

Atovercurrent/

 

Remote operator [F-22]

Digital operator

At instantaneous power failure

At low voltage

overvoltage/

At other

 

 

 

 

 

 

powermoduleerror

error

 

 

 

 

 

 

 

 

IPS TIME

0.3 to 25.0

Set an allowable instantaneous

 

 

 

 

power failure time.

 

 

 

 

 

 

 

 

 

 

 

IPS WAIT

0.3 to 100.0

Set a wait time after an instantaneous power failure/power restoration

 

 

 

 

in the retry mode or after an error.

 

 

 

 

 

 

 

 

 

 

 

IPS POWR

ALM

0

 

Tripping with an instantaneous

Tripping

Tripping

Tripping

 

 

 

 

power failure within the IPS

 

 

 

 

 

 

 

TIME. If an operation command

 

 

 

 

 

 

 

is issued for an instantaneous

 

 

 

 

 

 

 

power failure detected out of the

 

 

 

 

 

 

 

IPS TIME, restart the operation (0

 

 

 

 

 

 

 

Hz start).

 

 

 

 

 

 

 

 

 

 

 

 

FTP

1

 

The f matching stops with an

The f matching stops

The f

 

 

 

 

 

instantaneous power failure

if power is restored

matching is

 

 

 

 

 

detected within the IPS TIME.

within 40s.

retried.

 

 

 

 

 

The inverter trips with an

The inverter trips

 

 

 

 

 

 

instantaneous power failure

unless power is

 

 

 

 

 

 

detected out of the PIS TIME.

restored within 40s.

 

 

 

 

 

 

 

 

 

 

 

RST

2

 

The f matching is restarted if the

The f matching is

 

 

 

 

 

 

instantaneous power failure is

restarted if power is

 

 

 

 

 

 

within the IPS TIME. The

restored within 40s.

 

 

 

 

 

 

inverter trips if the instantaneous

The inverter trips

 

 

 

 

 

 

power failure is not within the

unless power is not

 

 

 

 

 

 

IPS TIME.

restored within 40s.

 

 

 

 

 

 

 

 

 

 

 

ZST

3

 

The inverter is restarted at 0 Hz if

The inverter is started

 

 

 

 

 

 

the instantaneous power failure is

at 0 Hz if power is

 

 

 

 

 

 

within the PIS TIME. The

restored within 40s.

 

 

 

 

 

 

inverter trips if the instantaneous

The inverter trips

 

 

 

 

 

 

power failure is not within the

unless power is

 

 

 

 

 

 

IPS TIME.

restored within 40s.

 

 

 

 

 

 

 

 

 

 

IPS TRIP

OFF

No retry at an instantaneous power failure and no trip

 

 

 

 

at low voltage during the inverter stop.

 

 

 

 

 

 

 

 

 

 

 

ON

Retry or under voltage trip is performed during the

 

 

 

 

inverter stop or running.

 

 

 

 

 

 

 

 

 

 

 

A-15