Hitachi J300U Series Base frequency setting, Maximum frequency, Frequency at the start of running

Models: J300U Series

1 145
Download 145 pages 53.04 Kb
Page 65
Image 65

Extension

function

code

Contents and display

Set the base frequency and maximum frequency. Setting example

Base frequency setting

Setting method

 

2

1

FUNC

 

 

Initial value

 

 

2

1

V 100%

FUNC

0

V

 

 

100%

 

 

0

 

 

60 Hz

60 Hz

120 Hz

f

 

f

Maximum frequency

(A62) base frequency

(A62) base frequency: 60 Hz

and (A63) maximum

(A63) maximum frequency:

frequency: 60 Hz

120 Hz

setting

Maximum frequency selection

Frequency command output frequency adjust

(O-L, OI-L)

 

 

 

(400)

 

 

When the frequency is set so that the base

 

frequency is larger than the maximum

 

frequency, the base frequency is forced

NOTE 1: When a frequency more than the base frequency 60 Hz

to be made equal to the maximum

 

is used, the motor is not a general purpose motor but

frequency at the start of running.

 

a special motor. Therefore, the maximum applicable

 

 

 

 

 

motor set value is different.

 

 

Freely setting range

 

When the kW display is the same, the inverter

V

capacity may be increased.

 

 

 

 

NOTE 2: Set the base frequency according to the specifications

100% (NOTE 3)

 

 

 

 

 

 

of the motor. When the base frequency is set to less

 

 

 

 

 

than 50 Hz, the motor may be burned.

0

30 Hz

60 Hz

120 Hz

400 Hz

 

 

 

 

 

 

 

f

 

Select 120 Hz or 400 Hz as the upper limit that can be set in the maximum frequency setting (A63).

➤ ➤

FUNC

Initial value

 

 

 

 

 

 

 

 

2

 

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Adjust the relationship between the external frequency command and the inverter output frequency.

:Voltage command (O-L)

:Current command (OI-L)

This function is factory-set to the appropriate position. If this setting is changed unnecessarily, the correct relationship between the external frequency command and output frequency is no longer maintained. This will result in poor control performance. Adjust the setting of this function only when the output frequency does not conform to the external command.

Adjustment method

 

 

 

 

 

Voltage command: Put voltage command (10V of 5V) to O-L terminal, and adjust

 

 

 

 

unit

output frequency comes to maximum.

 

 

 

 

 

 

 

 

 

 

 

Current command: Put current command (4-20mH) to OI-L terminal, and adjust

 

 

 

 

unit

output frequency comes to maximum.

 

 

 

 

 

 

 

 

 

 

 

 

7-25

Page 65
Image 65
Hitachi J300U Series instruction manual Base frequency setting, Maximum frequency, Frequency at the start of running