Measurement method for output voltage

(L1)(T1)

R U

(L2)

(T2)

S

V

(L3)(T3)

T W

Motor

Diode 600 V 0.1 A min. (200 V class)

1000 V 0.1 A min.

(400 V class)

220 kΩ

2WVDC

Fundamental wave effective value:

300 V (200 V class)

600 V (400 V class)

VAC=1.1×VDC

moving-coil type

10-7

Page 88
Image 88
Hitachi J300U Series instruction manual 10-7, Measurement method for output voltage