Control circuit

 

Terminal

 

Terminal description and function

Standard setting of

 

Remarks

 

symbol

 

intelligent terminal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FM

Frequency monitor

 

 

 

Dry contact

 

CM1

Common for monitor

 

 

 

Close: ON (run)

 

 

 

 

Open: OFF (stop)

 

 

 

 

 

 

 

 

 

PLC

Common terminal for the external power

 

 

 

Min. ON time:

 

 

source of the sequencer (PLC)

 

 

 

 

P24

Internal power source for the frequency

 

 

 

20 ms or more

 

 

 

 

 

 

 

 

 

monitor and intelligent input terminal

 

 

 

 

 

 

Input

FW

Forward operation

 

 

 

 

 

 

monitor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

signal

8

Intelligent input terminal 8

REV

Reverse operation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7

Intelligent input terminal 7

CF1

Multistage speed

 

 

 

 

 

 

 

 

 

(First stage)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6

Intelligent input terminal 6

USP

Prevention function of

 

 

 

 

 

 

 

 

 

restart upon power on.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

Intelligent input terminal 5

CH1

2 stage acc./dec.

 

 

 

 

 

 

 

 

 

 

 

 

Note:

 

4

Intelligent input terminal 4

FRS

Free run input signal

 

 

 

If the power is turned

 

 

 

 

 

 

 

 

 

on when the input

 

 

 

 

 

 

 

 

 

terminals 1 to 5 are

 

 

 

 

 

 

 

 

 

kept on, all the data

 

 

 

 

 

 

 

 

 

 

3

Intelligent input terminal 3

JG

Jogging

 

stored in the inverter

 

 

is initialized.

 

 

 

 

 

 

 

 

 

 

2

Intelligent input terminal 2

AT

Current input selection

 

Therefore, never turn

 

 

the power on in such

 

 

 

 

 

 

 

 

 

a state.

 

1

Intelligent input terminal 1

RS

Reset

(NOTE 1)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Frequency

H

Power supply for frequency command

 

 

 

10 VDC

command

 

 

 

 

 

 

 

 

 

O

Voltage frequency command

 

 

 

0-5 VDC (nominal), 0-10 VDC

input

 

 

 

(nominal)(Input impedance 30 kΩ)

 

 

 

 

 

 

 

 

OI

Current frequency command

 

 

 

DC 4-20 mA (nominal)

 

 

 

 

Input impedance 250Ω

 

 

 

 

 

 

 

 

 

L

Common for frequency command

 

 

 

 

 

 

Output

CM2

Common for intelligent output terminal

 

 

 

 

 

 

signal

 

 

 

 

 

 

 

 

 

 

12

Intelligent output signal 12

RUN

Run signal

27 VDC

 

 

11

Intelligent output signal 11

FA1

Frequency arrival signal

50 mA max

 

 

 

 

Fault alarm

AL0

 

 

 

 

 

 

 

 

 

 

Normal: AL0-AL1 close

Contact rating

 

 

 

output

AL1

 

 

Abnormal, Power off:

250 VAC

2.5 A (Resistor load) Min 100 VAC

 

 

 

AL0-AL1 open

 

 

0.2 A (cos¿=0.4)

10 mA

 

 

AL2 AL1

 

 

 

AL2

AL0

30 VDC

3.0 A (Resistor load) 5 VDC

 

 

 

 

 

 

 

 

 

 

 

0.7 A (cos¿=0.4)

100 mA

 

 

 

 

 

 

 

 

 

 

 

 

 

CAUTION

 

 

 

 

 

 

 

 

 

Alarm connection may contain hazardous live voltage even when inverter

is disconnected.

 

 

 

 

In case of removing flont cover for maintenance or inspection, confirm that incoming power

 

 

 

 

for alarm connection is surely disconnected.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE1: Terminal RS can use only contact a (normally open). It cannot use contact b (normally closed).

5-11

Page 31
Image 31
Hitachi J300U Series Common for monitor Close on run Open OFF stop, Reverse operation Intelligent input terminal, MA max