DR4300 Circular Chart Recorder

Main PCA

 

 

 

 

 

Main PCA

 

Pen 2

 

 

 

 

 

Pen 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7

TB1

7

TB2

TB1

TB2

L N

1It is the user’s responsibility to provide a switch and non-time delay (North America), quick-acting, high breaking capacity, Type F, (Europe) 1/2 A, 250 V fuse(s) or circuit-breaker as part of the installation.

2PROTECTIVE EARTH (Ground): Grounding of this recorder shall be in accordance with National and Local electrical codes.

3NOISELESS (Clean) EARTH (Ground): To minimize electrical noise and transients that may adversely affect the recorder, connection of the recorder terminal (located in the rear of the case) to a local earth (ground), using a No. 11 (4 mm2) braided copper conductor, is required.

 

 

24820

 

 

Ground

 

 

Screw

L

N

3

 

 

2

2

1

L1/H L2/N

100 Vac to 240 Vac

Figure 2-10 Power Wiring – Models With CE Mark

30

DR4300 Circular Chart Recorder Product Manual

12/03

Page 42
Image 42
Honeywell DR4300 manual Power Wiring Models With CE Mark