Appendix C - Setpoint Ramp/Soak

Programming and Operation

C.5 Run/Monitor the Program

Introduction

Prior to running the program, make sure all the SPPROG prompts under the SPRAMP set up group have been configured with the required data. (See Table C-1.)

“HOLD” appears periodically in the lower display indicating that the program is in the HOLD state.

ATTENTION

SP Programm parameters cannot be changed during RUN state (must be in HOLD state).

Run/Monitor functions

Table C-2lists all the functions required to run and monitor the program.

Table C-2 Run/Monitor Functions

Function

 

 

Press

 

 

 

 

 

Result

 

 

 

 

 

 

 

 

 

 

Set the Local Setpoint

 

 

 

 

 

You will see

 

 

 

 

 

 

 

 

 

 

 

 

 

input value

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SP and local setpoint value. (If control

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

set up group NumSPs = TWO, make sure the recorder is

 

 

 

 

 

 

set to use setpoint 1 by checking that operating

 

 

 

 

 

 

parameter UseSP1 is displayed.

 

 

 

 

 

 

If UseSP2 is displayed, use ▲ or ▼to switch to UseSP1.)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

To set the Local Setpoint value to where you want the

 

 

 

 

 

 

 

 

 

 

 

 

program to start out.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Selecting the Program

 

 

 

 

 

until

 

 

 

 

to be Run

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

To select the program where n is the program number 1

 

 

 

 

 

 

 

 

 

 

 

 

through 4.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 