4.3.11 Control Parameters Set Up Group

Introduction

If the recorder hardware supports outputs, the functions in this group are used to configure how the recorder will control the process. (If configuring a limit controller, see Subsection 4.3.22 for special limit control configuration parameters.)

Control group prompts

Table 4-9lists all the function prompts in the control set up group. For a 2-pen recorder, the desired input

channel is displayed on the left side of the operator interface. Press FUNC to select channel. Press

SETUP key until “CONTRL” appears in the lower display. Press FUNC key to select the parameters.

Table 4-9 Control Parameter Definitions

Lower Display

 

Upper Display

Parameter

Prompt

Range of Setting

Definition

 

 

or Selection

 

 

 

 

 

CONTRL

ENAB

[factory setting]

Enables control.

 

DIS

Disables control. If control is disabled here, the rest of the

 

 

 

functions in this group will not be displayed. All alarm

 

 

 

group functions will be displayed.

 

 

 

NumSPs

ONE [factory setting]

NUMBER OF SETPOINTS—If this is set to TWO, then

 

TWO

 

the operator will be able to select the setpoint using the

 

 

UseSPn operating parameter prompt.

 

 

 

 

OUTALG

 

 

OUTPUT ALGORITHM —Use to specify the type of

 

 

 

output.

 

RLY

[factory setting]

RELAY SIMPLEX—Type of output using one SPDT

 

 

 

relay. Its contacts can be wired for normally open (NO) or

 

 

 

normally closed (NC) action.

 

 

 

Control group function “HYST” is affected.

 

 

 

The second relay is available for alarming, and alarm

 

 

 

group functions will be displayed for Alarm 2.

 

RLYD

 

RELAY DUPLEX—Type of output using two SPDT

 

 

 

relays. Its contacts can be wired for normally open (NO)

 

 

 

or normally closed (NC) action.

 

 

 

Control group function "DBAND" is affected.

 

 

 

No relay is available for alarming, and no alarm group

 

 

 

functions will be displayed.

 

CUR

 

CURRENT SIMPLEX—Type of output using one 4 mA to

 

 

 

20 mA signal that can be fed to a positive or negative

 

 

 

grounded load of 0 to 600 ohms. The current output

 

 

 

signal can be recalibrated as described in Section 5 to

 

 

 

use any range within 4 mA to 20 mA to represent 0 to 100

 

 

 

% output.

 

CurT

 

CURRENT/TIME DUPLEX (Relay = Heat)—Variation of

 

 

 

duplex with current active for 0 % to 50 % output (tuning

 

 

 

set 2) and relay active 50 % to 100 % output (tuning set

 

 

 

1).

 

 

 

Control group functions “CURRNG” and "DBAND" are

 

 

 

affected.

 

 

 

 

94

DR4300 Circular Chart Recorder Product Manual