Configuration, Startup, and Operation

 

 

 

 

 

 

of Recorder with Display

 

 

 

 

 

 

 

 

 

Lower Display

Upper Display

 

 

Parameter

 

 

Prompt

Range of Setting

 

 

Definition

 

 

 

or Selection

 

 

 

 

 

 

 

 

 

 

 

 

PB2

0.1 % to 999.9 %

PB2 or GAIN 2, RATE2T, and I2 MIN or I2 RPM

 

 

or

or

These parallel their counterparts already described.

 

 

GAIN 2

0.1 to 999.9

 

 

 

 

 

 

[factory setting = 1.0]

 

ATTENTION

If control group parameter “OUTALG”

 

 

 

 

 

 

 

 

 

is “RLYD” (relay duplex), “Tcur” (time/current duplex), or

 

 

RATE2T

0.08 to 10.00 minutes

“CurT” (current/time duplex), and you are using the

 

 

 

0.08 or less = OFF

recorder in a heat/cool application, these parameters are

 

 

 

 

used for cooling control.

 

 

 

[factory setting = 0.0]

 

 

 

 

 

 

 

 

 

 

 

 

I2 MIN

0.02 to 50.00

 

 

 

 

 

or

[factory setting = 0.02]

 

 

 

 

 

I2 RPM

 

 

 

 

 

 

 

 

 

 

 

The following parameters are used for time proportional control, and are available only if:

the control type specified in the control set up group using the “CTRALG” (control algorithm) parameter is “PIDA” or “PDMR”

and

the output algorithm specified in the control set up group using the “OUTALG” parameter is

“RLY” , “RLYD”, “CurT”, or “Tcur”. In the case of “CurT” and “Tcur”, the cycle parameters apply only to the time-proportioned output.

CYC TI

0 seconds to 120 seconds

CYCLE TIMER FOR RELAY 1—Use this to specify

 

[factory setting = 4]

length of total cycle time for time proportional control

 

(proportional control using relay action rather than current

 

 

output). In time proportional control the output (0 % to 100

 

 

%) signifies the portion of the cycle for which the relay is

 

 

on (“duty cycle”) to achieve the desired setpoint. For

 

 

example, with a 10-second cycle time and an output value

 

 

of 10 %, the relay would be on for 1 second and off for 9

 

 

seconds.

 

 

 

 

 

 

 

 

 

ATTENTION

If control group parameter “OUTALG” is

 

 

 

 

 

 

“RLYD” (relay duplex), and you are using the recorder in

 

 

a heat/cool application, CYC TI is used for heat control.

 

 

Cooling control would use CYC2TI.

 

 

 

CYC2TI

0 seconds to 120 seconds

CYCLE TIMER FOR RELAY 2—This prompt will be

 

[factory setting = 4]

displayed only if the control group parameter “OUTALG”

 

is set to RLYD (relay duplex).

 

 

 

 

 

 

 

 

ATTENTION

If you are using the recorder in a

 

 

 

 

 

 

heat/cool application, CYC2TI is used for control of

 

 

cooling.

 

 

 

 

 

 

12/03

DR4300 Circular Chart Recorder Product Manual

103

Page 115
Image 115
Honeywell DR4300 manual Used for cooling control, 02 to, Cycle Timer for Relay 1 -Use this to specify