Configuration, Startup, and Operation of Recorder with Display

4.5.2.4 Viewing and Changing Alarm Setpoints

Introduction

If the recorder hardware supports outputs, one or both relays can be used for alarming. An alarm is an indication that an event specified during configuration (process variable, for example) has exceeded one or more alarm limits. There are two alarms available for each pen (assuming no relay is being used for control). Each alarm has two setpoints. There are two alarm output selections, high and low. During configuration, each alarm setpoint is configured to alarm either high or low.

The alarm setpoints can be changed by the operator if the alarm parameters are not locked (see Subsection 4.3.19). If a recorder output is being used for control, that output is not available as an alarm and the prompts will not appear.

Procedure

The procedure for displaying and changing the alarm setpoints is listed in Table 4-31.

Table 4-31 Procedure for Displaying or Changing the Alarm Setpoints

Step

Operation

Press

Action/Result

1

Access the Alarm Set

SET

Until you see:

 

Up group

 

Upper Display

 

UP

 

 

 

 

 

SET

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Lower Display

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ALARMS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

Access the Alarm

 

Until you display the desired alarm setpoint and its

 

 

Setpoint Values

FUNC

value. Their order of appearance is shown below.

 

 

 

 

 

Upper Display

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The alarm setpoint

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

value

 

 

 

 

 

 

 

 

 

 

 

 

 

Lower Display

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A1S1 VA = (Alarm 1, Setpoint 1 value)

 

 

 

 

 

A1S2 VA = (Alarm 1, Setpoint 2 value)

 

 

 

 

 

A2S1 VA = (Alarm 2, Setpoint 1 value)

 

 

 

 

 

A2S2 VA = (Alarm 2, Setpoint 2 value)

 

 

 

 

 

 

 

 

 

Change any alarm setpoint value you select in the

 

 

 

or

upper display.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

Return to normal

 

Returns to normal operation.

 

 

operation

DISP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12/03

DR4300 Circular Chart Recorder Product Manual

135