Input and Output Calibration for Recorder with Display

5.Input and Output Calibration for Recorder with Display

5.1Overview

Introduction

This section explains how to field calibrate analog inputs, as well as a 4 to 20 mA current output for a model having a display and keypad.

Because the recorder stores both factory and field calibration values for inputs in memory, you can easily select either factory or field calibration values for use by the recorder using the procedure given in Subsection 4.5.2.5.

To calibrate an input:

Determine the minimum and maximum range values to be used for calibration (see Subsection 5.2).

Prepare to calibrate (see Subsection 5.3).

Set up and wire the input for calibration (see Subsection 5.4).

Use the parameters in the calibration set up group to store field calibration values in the recorder’s memory (see Subsection 5.5).

What’s in this section?

The following is a list of the topics covered in this section.

 

Topic

See Page

 

 

 

5.1

Overview

141

 

 

 

5.2

Input Calibration Minimum and Maximum Range Values

142

 

 

 

5.3

Input Calibration Preliminary Information

144

 

 

 

5.4

Input Calibration Set Up and Wiring

146

 

 

 

5.5

Input Calibration Procedure

151

 

 

 

5.6

Current Output Calibration

153

 

 

 

WARNING—SHOCK HAZARD

!

 

INPUT CALIBRATION MAY REQUIRE ACCESS TO HAZARDOUS LIVE CIRCUITS, AND SHOULD ONLY BE PERFORMED BY QUALIFIED SERVICE PERSONNEL. MORE THAN ONE SWITCH MAY BE REQUIRED TO DE-ENERGIZE UNIT BEFORE CALIBRATION.

12/03

DR4300 Circular Chart Recorder Product Manual

141

Page 153
Image 153
Honeywell Input and Output Calibration for Recorder with Display, DR4300 Circular Chart Recorder Product Manual 141