DR4300 Circular Chart Recorder

Lower Display

Upper Display

Parameter

 

Prompt

Range of Setting

Definition

 

 

or Selection

 

 

AUXOUT

DE

DEVIATION (Process Variable minus Setpoint)

(continued)

 

Represents –100 % to +100 % of the selected PV span in

 

 

engineering units. FOR EXAMPLE:

 

 

 

Type “T” Thermocouple

 

 

 

PV range = –300 °F to +700 °F

 

 

PV span =

1000 °F

 

 

Deviation range = –1000 °F to +1000 °F

 

 

If PV =

500 °F

 

 

and SP =

650 °F

 

 

then Deviation Display =

–150 °F

 

 

Auxiliary Output =

42.5 %

 

 

NOTE: A deviation of 0°F yields an auxiliary output of

 

 

50 %.

 

 

 

 

4mA VA

Low Scale Value within the

AUXILIARY OUTPUT LOW SCALING FACTOR—Use a

 

range of the selected variable

value in engineering units for all selections above except

 

to represent 4 mA

Output.

 

 

[factory setting = 0]

Use value in percent (%) for Output. (Output can be

 

 

between –5 % and +105 %.)

 

 

 

 

20mA V

High Scale Value within the

AUXILIARY OUTPUT HIGH SCALING FACTOR—Use a

 

range of the selected variable

value in engineering units for all selections above except

 

to represent 20 mA

Output.

 

 

[factory setting = 100]

Use a value in percent (%) for Output. (Output can be

 

 

between –5 % and +105 %.)

 

 

 

*When Deviation is selected, only one operating

 

 

parameter will be entered. This value represents the

 

 

deviation level that will produce 20 mA output. Zero

 

 

deviation will produce a center scale (12 mA) output. A

 

 

negative deviation equal in magnitude to the Auxiliary

 

 

Output High Value will provide a low end (4 mA) output.

 

 

 

 

110

DR4300 Circular Chart Recorder Product Manual

12/03

Page 122
Image 122
Honeywell DR4300 manual Deviation Process Variable minus Setpoint, 4mA VA, Auxiliary Output LOW Scaling FACTOR-Use a