Mitsumi electronic PKA-A18HA4, PKA-A12HA4 service manual System constraint, Request Code List

Models: PKA-A18HA4 PKA-A12HA4

1 36
Download 36 pages 12.47 Kb
Page 27
Image 27
(1) Request Code List

Manual background System constraint

· This function is available only in cooling mode.

Ex.) Set temp. by R/C = 20:(68°F) Set point = 26:(79°F)

When request code number is “323”.

26:

 

2nd unit Cut-in

 

(79°F)

 

 

4 degree C

 

 

 

 

 

 

 

 

(7.5 degreeF)

22:

 

2nd unit Cut-out

 

(71.5°F)

 

 

 

20:

 

 

 

 

 

 

(68°F)

 

 

 

[2nd stage cut-in function]··· Request code number "322~324"

 

 

 

 

Room temp. Set point

Room temp. < Set point -4 (-7.5°F)

 

 

Start operation

Sub unit start operation

Sub unit stop

Main

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

unit

 

 

 

 

 

 

 

 

 

 

Run

 

 

 

 

 

IC-1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Sub

 

 

 

 

 

 

 

 

unit

 

 

Stop

 

Run

 

Stop

IC-2

 

 

 

 

 

 

 

 

10-1-2. How to set rotation function (Back-up function, 2nd stage cut-in function)

You can set these functions by wired remote controller. (Maintenance monitor)

NOTE

Both main and sub unit should be set in same setting.

Every time replacing indoor controller board for servicing, the function should be set again.

(1) Request Code List

Rotation setting

Setting No.

Setting contents

Initial

(Request code)

setting

 

No.1

Monitoring the request code of current setting.

 

(310)

 

 

 

No.2

Rotation and Back-up OFF (Normal group control operation)

 

(311)

 

 

 

No.3

Back-up function only

 

(312)

 

 

 

No.4

Rotation ON (Alternating interval = 1day) and back up function

 

(313)

 

 

 

No.5

Rotation ON (Alternating interval = 3day) and back up function

 

(314)

 

 

 

No.6

Rotation ON (Alternating interval = 5day) and back up function

 

(315)

 

 

 

No.7

Rotation ON (Alternating interval = 7day) and back up function

 

(316)

 

 

 

No.8

Rotation ON (Alternating interval = 14day) and back up function

 

(317)

 

 

 

No.9

Rotation ON (Alternating interval = 28day) and back up function

 

(318)

 

 

 

2nd stage cut-in setting

Setting No.

Setting contents

Initial

(Request code)

setting

 

No.1

Monitoring the request code of current setting.

 

(320)

 

 

 

No.2

Cut-in function OFF

 

(321)

 

 

 

No.3

Cut-in Function ON(Set point = Set temp.+ 4°C(7.5°F))

 

(322)

 

 

 

No.4

Cut-in Function ON(Set point = Set temp.+ 6°C(10.8°F))

 

(323)

 

 

 

No.5

Cut-in Function ON(Set point = Set temp.+ 8°C(14.4°F))

 

(324)

 

 

 

27

Page 27
Image 27
Mitsumi electronic PKA-A18HA4, PKA-A12HA4 service manual System constraint, Request Code List