Mitsumi electronic PKA-A12HA4 Self-Diagnosisaction Table, Error Code, Cause, Countermeasure

Models: PKA-A18HA4 PKA-A12HA4

1 36
Download 36 pages 12.47 Kb
Page 16
Image 16
9-3. SELF-DIAGNOSIS ACTION TABLE

9-3. SELF-DIAGNOSIS ACTION TABLE

Note: Refer to the manual of outdoor unit for the details of display such as F, U, and other E.

Error Code

Abnormal point and detection method

Cause

 

Countermeasure

 

Room temperature thermistor (TH1)

Defective thermistor

– Check resistance value of thermistor.

 

The unit is in 3-minute resume

characteristics

0

• • • • • • • • • • 15.0k

 

prevention mode if short/open of

Contact failure of connector

10

• • • • • • • • • • • • 9.6k

 

thermistor is detected. Abnormal if the

(CN20) on the indoor controller

20

• • • • • • • • • • • • 6.3k

 

unit does not reset normally after 3 min-

board (Insert failure)

30

• • • • • • • • • • • • 4.3k

 

utes. (The unit returns to normal opera-

Breaking of wire or contact

40

• • • • • • • • • • •3.0k

 

tion, if it has been reset normally.)

failure of thermistor wiring

If you put force on (draw or bend) the lead wire

 

Constantly detected during cooling,

Defective indoor controller

while measuring resistance value of thermistor,

 

drying, and heating operation.

board

breaking of wire or contact failure can be

 

Short: 90

 

detected.

 

 

P1

Open: -40

 

Check contact failure of connector (CN20) on

 

 

the indoor controller board. Refer to 9-7.

 

 

 

Turn the power on again and check restart

 

 

 

after inserting connector again.

 

 

 

Check room temperature display on remote

 

 

 

controller.

 

 

 

 

 

Replace indoor controller board if there is

 

 

 

abnormal difference with actual room

 

 

 

temperature.

 

 

 

 

Turn the power off, and on again to operate

 

 

 

after check.

 

 

 

 

 

 

 

Pipe temperature thermistor/Liquid

Defective thermistor

– Check resistance value of thermistor.

 

(TH2)

characteristics

For characteristics, refer to (P1) above.

 

The unit is in 3-minute resume

Contact failure of connector

Check contact failure of connector (CN44) on

 

prevention mode if short/open of

(CN44) on the indoor controller

the indoor controller board. Refer to 9-7.

 

thermistor is detected. Abnormal if the

board (Insert failure)

Turn the power on and check restart after

 

unit does not reset normally after 3 min-

Breaking of wire or contact

inserting connector again.

 

utes. (The unit returns to normal opera-

failure of thermistor wiring

Check pipe <liquid> temperature with remote

 

tion, if it has been reset normally.)

Defective refrigerant circuit is

controller in test run mode. If pipe <liquid>

P2

Constantly detected during cooling,

causing thermistor tempera-

temperature is extremely low (in cooling

drying, and heating (except defrosting)

ture of 90

mode) or high (in heating mode), refrigerant

 

 

operation.

-40

circuit may have defect.

 

Short: 90

Defective indoor controller

Check pipe <liquid> temperature with remote

 

Open: -40

board

controller in test run mode. If there is extremely

 

 

 

difference with actual pipe <liquid> temperature,

 

 

 

replace indoor controller board.

 

 

 

Turn the power off, and on again to operate

 

 

 

after check.

 

 

 

 

 

 

 

Contact failure of drain float switch (CN4F)

Contact failure of connector

Check contact failure of float switch connec-

 

Extract when the connector of drain float

(Insert failure)

tor.

 

 

P4

switch is disconnected.

 

Turn the power on again and check after

( and of connector CN4F is not

 

inserting connector again.

(5701)

 

short-circuited.)

Defective indoor controller

Operate with connector (CN4F) short-circuited.

 

 

Constantly detected during operation.

board

Replace indoor controller board if abnormality

 

 

 

reappears.

 

 

 

 

 

 

 

Drain overflow protection operation

Malfunction of drain pump

Check if drain pump works.

 

Suspensive abnormality, if drain float

Defective drain

Check drain function.

 

 

switch is detected to be underwater for

Clogged drain pump

 

 

 

 

1 minute and 30 seconds continuously

Clogged drain pipe

 

 

 

 

with drain pump on.

Defective drain float switch

Remove drain float switch connector CN4F

 

Turn off compressor and indoor fan.

Catch of drain float switch or

and check if it is short (Switch On) with the

 

Drain pump is abnormal if the condition

malfunction of moving parts

moving part of float switch UP, or OPEN with

 

above is detected during suspensive

cause drain float switch to be

the moving part of float switch down.

 

abnormality.

detected under water (Switch

Replace float switch if it is short with the

P5

Constantly detected during drain pump

On)

moving part of float switch down.

 

operation.

Defective indoor-controller

Replace indoor controller board if it is short-

 

 

board

circuited between -

of the drain float

 

 

 

switch connector CN4F and abnormality

 

 

 

reappears.

 

 

 

 

 

It is not abnormal if there is no problem about

 

 

 

the above-mentioned

~

 

 

 

Turn the power off, and on again to operate

 

 

 

after check.

 

 

 

 

 

 

 

 

16

Page 16
Image 16
Mitsumi electronic PKA-A12HA4, PKA-A18HA4 service manual Self-Diagnosisaction Table, Error Code, Cause, Countermeasure