Error Code Abnormal point and detection method | Cause | Countermeasure | |
| Freezing/overheating protection is | (Cooling or drying mode) | (Cooling or drying mode) |
| operating | Clogged filter (reduced airflow) | Check clogs of the filter. |
| Freezing protection (Cooling mode) | Short cycle of air path | Remove blockage. |
| The unit is in | Low load (low temperature) |
|
| mode if pipe <liquid or condenser/evapo- | operation out of the tolerance |
|
| rator> temperature stays under |
| |
| range |
| |
| the compressor started. Abnormal if it | Defective indoor fan motor | Refer to |
| • Fan motor is defective. |
| |
|
|
| |
| again within 16 minutes after | • Indoor controller board is defec- |
|
| resume prevention mode. | tive. | Check outdoor fan motor. |
|
| Defective outdoor fan control | |
|
| Overcharge of refrigerant | Check operating condition of refrigerant |
|
| Defective refrigerant circuit | circuit. |
|
| (clogs) |
|
| Overheating protection (Heating mode) | (Heating mode) | (Heating mode) |
| Clogged filter (reduced airflow) | Check clogs of the filter. | |
| The units is in | ||
| Short cycle of air path | Remove blockage. | |
| prevention mode if pipe <liquid or | ||
| Overload (high temperature) |
| |
P6 | condenser/evaporator> temperature is |
| |
operation out of the tolerance |
| ||
detected as over 70°C[158°F] after the |
| ||
| range |
| |
| compressor started. Abnormal if the |
| |
| Defective indoor fan motor | Refer to | |
| temperature of over 70°C[158°F] is | ||
| • Fan motor is defective. |
| |
| detected again within 10 minutes after |
| |
| • Indoor controller board is defec- |
| |
| 6 minute resume prevention mode. |
| |
| tive. |
| |
|
| Check outdoor fan motor. | |
|
| Defective outdoor fan control | |
|
| Overcharge of refrigerant | ~ Check operating condition of refrigerant |
|
| Defective refrigerant circuit | circuit. |
|
| (clogs) |
|
|
| Bypass circuit of outdoor unit |
|
|
| is defective. |
|
| Pipe temperature |
| Slight temperature difference | ~ Check pipe <liquid or condenser/evap- |
|
| <Cooling mode> |
| between indoor room | orator> temperature with room tempera- | |
| Detected as abnormal when the pipe tem- | temperature and pipe <liquid | ture display on remote controller and |
| |
| perature is not in the cooling range 3 min- | or condenser/evaporator> | outdoor controller circuit board. |
| |
| utes after compressor start and 6 minutes | temperature thermistor | Pipe <liquid or condenser/evaporator> | ||
| after the liquid or condenser/evaporator pipe | • Shortage of refrigerant | temperature display is indicated by set- | ||
| is out of cooling range. |
| • Disconnected holder of pipe | ting SW2 of outdoor controller circuit |
|
| Note 1) It takes at least 9 minutes to detect. | <liquid or condenser/ | board as follows. |
| |
| Note 2) Abnormality P8 is not detected in | evaporator> thermistor |
| ) | |
| drying mode. |
| • Defective refrigerant circuit | Conduct temperature check with outdoor | |
| Cooling range : - | Converse connection of | controller circuit board after connecting | ||
| TH: Lower temperature between liquid pipe | extension pipe (on plural units | |||
| temperature (TH2) and condenser/ | connection) |
|
| |
| evaporator temperature (TH5) | Converse wiring of indoor/ | Check converse connection of extension | ||
| TH1: Intake temperature |
| outdoor unit connecting wire | pipe or converse wiring of indoor/outdoor | |
P8 | <Heating mode> |
| (on plural units connection) | unit connecting wire. |
|
| Defective detection of indoor |
|
| ||
| When 10 seconds have passed after the | room temperature and pipe |
|
| |
| compressor starts operation and the hot | <condenser/evaporator> |
|
| |
| adjustment mode has finished, the unit is | temperature thermistor |
|
| |
| detected as abnormal when condenser/ | Stop valve is not opened |
|
| |
| evaporator pipe temperature is not in heat- | completely. |
|
| |
| ing range within 20 minutes. |
|
|
|
|
| Note 3) It takes at least 27 minutes to |
|
|
| |
| detect abnormality. |
|
|
|
|
| Note 4) It excludes the period of defrosting |
|
|
| |
| (Detection restarts when defrosting |
|
|
| |
| mode is over) |
|
|
|
|
| Heating range : |
|
|
|