•Refer to the following tables for details on the check codes. [Output pattern A]
Beeper sounds Beep |
|
| Beep | Beep | Beep | Beep |
|
| Beep | Beep | ||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
OPERATION |
|
|
|
|
|
|
| 1st |
| 2nd |
|
| 3rd |
|
| nth |
|
|
|
|
| 1st |
|
| 2nd · · · Repeated | |
INDICATOR |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
lamp blink |
|
|
|
| Off |
|
| On | On |
| On |
| On | Off |
|
| On |
| On | |||||||
pattern | 0.5 sec. Approx. 2.5 sec. 0.5 sec. |
| 0.5 sec. | |||||||||||||||||||||||
| starts |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
| (Start signal | Number of blinks/beeps in pattern indicates the check | Number of blinks/beeps in pattern indicates | |||||||||||||||||||||||
| received) | |||||||||||||||||||||||||
| code in the following table (i.e., n=5 for “P5”) |
| the check code in the following table | |||||||||||||||||||||||
|
|
|
|
|
|
[Output pattern B]
Beeper sounds Beep |
|
|
|
| ||||
OPERATION |
|
|
|
|
|
|
|
|
INDICATOR |
|
|
|
|
|
|
|
|
lamp blink |
|
|
|
|
|
|
|
|
|
|
|
| Off |
|
| ||
pattern | Approx. 2.5 sec. |
|
|
starts (Start signal received)
|
| Beep | Beep | Beep |
| Beep |
|
|
|
|
|
| Beep | Beep | ||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 1st |
|
| 2nd |
|
| 3rd |
|
|
| nth |
|
|
|
|
|
|
|
|
| 1st |
| 2nd · · · Repeated | |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||
On |
|
| On |
| On |
| On |
|
| On |
| Off |
| On |
| On | On | |||||||||
Approx. 3 sec. |
| 0.5 sec. 0.5 sec. 0.5 sec. |
| 0.5 sec. | Approx. 2.5 sec. |
| Approx. 3 sec. | 0.5 sec. | 0.5 sec. | |||||||||||||||||
Number of blinks/beeps in pattern indicates the check |
| Number of blinks/beeps in pattern indicates | ||||||||||||||||||||||||
code in the following table (i.e., n=5 for “U2”) |
| the check code in the following table |
[Output pattern A] Errors detected by indoor unit
IR wireless remote controller | Wired remote controller |
|
|
|
| |
Beeper sounds/OPERATION |
| Symptom | Remark | |||
INDICATOR lamp blinks | Check code | |||||
|
|
|
| |||
(Number of times) |
|
|
|
|
| |
1 | P1 | Intake sensor error |
|
|
| |
2 | P2 | Pipe (TH2) sensor error |
|
|
| |
P9 | Pipe (TH5) sensor error |
|
|
| ||
|
|
|
| |||
3 | E6,E7 | Indoor/outdoor unit communication error |
|
|
| |
4 | P4 | Float switch connector (CN4F) open |
|
|
| |
5 | P5 | Drain pump error |
|
|
| |
PA | Forced compressor stop(due to water leakage abnormality) |
|
|
| ||
|
|
| ||||
|
|
|
| |||
6 | P6 | Freezing/Overheating protection operation |
|
|
| |
7 | EE | Communication error between indoor and outdoor units |
|
|
| |
8 | P8 | Pipe temperature error |
|
|
| |
9 | E4, E5 | Remote controller signal receiving error |
|
|
| |
10 | – | – |
|
|
| |
11 | – | – |
|
|
| |
12 | Fb | Indoor unit control system error (memory error, etc.) |
|
|
| |
– | E0, E3 | Remote controller transmission error |
|
|
| |
– | E1, E2 | Remote controller control board error |
|
|
|
[Output pattern B] Errors detected by unit other than indoor unit (outdoor unit, etc.)
IR wireless remote controller | Wired remote controller |
|
| |
Beeper sounds/OPERATION |
| Symptom | Remark | |
INDICATOR lamp blinks | Check code | |||
|
| |||
(Number of times) |
|
|
| |
1 | E9 | Indoor/outdoor unit communication error |
| |
(Transmitting error) (Outdoor unit) |
| |||
|
|
| ||
2 | UP | Compressor overcurrent interruption |
| |
3 | U3,U4 | Open/short of outdoor unit thermistors | For details, check | |
4 | UF | Compressor overcurrent interruption (When compressor locked) | ||
the LED display | ||||
|
| Abnormal high discharging temperature/49C operated/ | ||
5 | U2 | of the outdoor | ||
insufficient refrigerant | ||||
|
| controller board. | ||
|
| Abnormal high pressure (63H operated)/Overheating | ||
6 | U1,Ud | As for outdoor | ||
protection operation | ||||
|
| unit, refer to | ||
7 | U5 | Abnormal temperature of heatsink | ||
outdoor unit's | ||||
8 | U8 | Outdoor unit fan protection stop | service manual. | |
9 | U6 | Compressor overcurrent interruption/Abnormal of power module |
| |
10 | U7 | Abnormality of superheat due to low discharge temperature |
| |
11 | U9,UH | Abnormality such as overvoltage or voltage shortage and |
| |
abnormal synchronous signal to main circuit/Current sensor error |
| |||
|
|
| ||
12 | – | – |
| |
13 | – | – |
| |
14 | Others | Other errors (Refer to the technical manual for the outdoor unit.) |
|
*1 If the beeper does not sound again after the initial 2 beeps to confirm the
*2 If the beeper sounds 3 times continuously “beep, beep, beep (0.4 + 0.4 + 0.4 sec.)” after the initial 2 beeps to confirm the
14