Check method of DC fan motor (fan motor/indoor controller circuit board)
Notes
·High voltage is applied to the connecter (CNMF) for the fan motor. Pay attention to the service.
·Do not pull out the connector (CNMF) for the motor with the power supply on. (It causes trouble of the indoor controller circuit board and fan motor.)
Self check
Symptom : The indoor fan cannot rotate.
Wiring contact check
Contact of fan motor connector (CNMF)
Is there contact failure? | Yes | Wiring recovery |
No
Power supply check (Remove the connector (CNMF))
Measure the voltage in the indoor controller circuit board.
TEST POINT : VDC (between 1 (+) and 3
TEST POINT : VCC (between 4 (+) and 3
Is the voltage normal? | No |
Yes
Sensor signal check
Measure the voltage between CNMF and DC 0V and DC 15V in the indoor controller circuit board.
Indoor controller board fuse check
Is the fuse normal? |
| No | Replace | |
|
| |||
|
| the fuse. | ||
Yes |
|
| ||
|
| OK | ||
Replace the indoor | NG |
| ||
Check the operation | ||||
controller board. |
| |||
|
|
| ||
|
| OK |
| |
Check the operation |
| END |
|
NG
Replace the fan motor.
END
Does the voltage repeat | No |
| |
DC 0V and DC 15V? |
|
Yes |
|
Replace the indoor |
|
controller board. |
|
| OK |
Check the operation | END |
NG |
|
Replace the fan motor. |
|
Replace the fan motor.
YesOK
Check the operation of fan. | END |
NG
Replace the indoor controller board.
23