10 SPECIAL FUNCTION
This function is only available when using wired remote controller.
10-1-1. Operation
(1)Rotation function (and
·Main and sub units operate alternately according to the interval of rotation setting.
w Main and sub unit should be set by refrigerant address. (Outdoor Dip switch setting)
Refrigerant address "00" Main unit
Refrigerant address "01" Sub unit
· When error occurs to one unit, another unit will start operation.
System constraint
·This function is available only by the grouping control system (INDOOR UNIT: OUTDOOR UNIT=1:1) of 2 refrigerant groups. (Refer to Fig. 1)
·Main indoor unit should be connected for wired remote controller and the transmission line (TB5) for main and sub unit should also be connected. (Refer to Fig. 1)
(This function cannot be set by IR wireless remote controller.)
·Set refrigerant address of each unit. (Dip switch on the outdoor unit ··· Refrigerant address 00/01)
Operation pattern
|
| Start operation | Error occurs on main unit. | ||
|
| Main Sub | |||
Main |
|
|
|
|
|
|
|
|
|
| |
unit |
|
|
|
| Abnormal condition |
|
| Run |
| ||
|
|
| |||
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
Sub |
|
|
|
|
|
unit |
|
| Stop |
| Run |
|
|
|
|
| |
|
|
|
|
|
|
[Rotation function] &
Error occurs on main unit.
Fig. 1 Refrigerant address
| "00" |
|
|
| ||
|
|
|
|
|
|
|
|
|
|
| |||
Main |
|
|
|
|
|
|
3(2) |
| |||||
unit |
| |||||
|
|
|
|
|
| |
|
|
|
|
|
| |
|
|
|
| |||
|
|
|
|
|
|
|
| 2 |
|
|
|
| 2 |
|
|
|
|
|
| |
|
| RC |
|
|
| |
|
|
|
|
|
|
|
Refrigerant address "01"
Sub
3(2) unit
Start operation | Main Sub | Sub Main Main Sub |
OC : Outdoor unit
Main
unit
Sub unit
Run
Stop
1~28 days
Stop
Run
1~28 days
Run
Stop
Abnormal condition
Run
IC : Indoor unit
RC : Wired remote controller
(Ex:When the request code number is "313", each unit operates alternately in daily cycle.)
Note:
·When the uint is restarted to operate after turning off the power or OFF operation, the unit which was operating will start oper- ation.
·To operate the main unit, refer to the
(2)2nd stage cut-in function Outline of functions
·When the 1st unit can NOT supply with sufficient capacity for exceptionally
·Once the actual room temperature goes down to 4 degrees C (7.5 degrees F) below set point*, the 2nd unit stops operation automatically.
(* set point = set temperature by R/C (remote controller) + 4, 6, 8:(7.5, 10.8, 14.4°F) (selectable))
·Number of operating units is determined according to the room temperature and set point.
·When room temperature becomes higher than set point, standby unit starts. (2 units operation)
·When room temperature falls below set point
26