Nesco 6033 owner manual Guidelines for Exhaust Venting Systems Design

Page 7

GUIDELINES FOR EXHAUST VENTING SYSTEMS DESIGN continued...

Distance from bottom of termination and grade-1ft./305mm minimum. This is conditional upon the plants and nature of grade surface. The exhaust gases are not hot enough to ignite grass, plants or shrubs located in the vicinity of the termination. The grade surface must not be a lawn. Distance from bottom of termination and public walkway is 7ft./ 2.1m minimum.

Distance to combustible materials-2ft./610mm. This includes adjacent building, fences, protruding parts of the struc- ture, roof overhang, plants and shrubs, etc.

It is recommended that a single or double clean-out “tee” be installed at every 90° junction to enable collection of fly ash and to permit periodic cleaning of the exhaust system. 90° elbows accumulate fly ash and soot thereby reducing exhaust flow and performance of the stove.

Total length of horizontal vent must not exceed 48”(4ft.)/1,200mm. All joints in the vent system must be fastened by at least 3 screws, and all joints must be sealed with RTV silicone sealer to be airtight.

When venting into an existing masonry or factory built chimney, the chimney must be cleaned, with all creosote re- moved. The chimney must be a type suited for solid fuel. WARNING: The chimney and the chimney connections must be kept clean an in good condition.

The “PL” vent or single wall stainless exhaust system must be installed so as to be GAS TIGHT! The vent manufacturer’s installation procedures must be followed. In addition, pipe connections, joints and all pipe seams within the home should be sealed with high temperature RTV silicone sealer.

The area where the chimney penetrates to the exterior of the home must be sealed with silicone or other means to maintain the vapor barrier between the exterior and the interior of the home.

Where installations will be made in locations above 2,000 feet, it is recommended that your stove be installed with 4” pell vent. At elevations above 3,000 feet, it is mandatory that a 4” pell vent be used for your installation.

NOTE: These are guidelines only. Proper venting is accomplished by design and common sense. In most installations 3” inch diameter venting is adequate. If it does not vent properly you will have to change it to 4”.

DO NOT CONNECT TO ANY AIR DISTRIBUTION DUCT OR SYSTEM

USSC

7

Image 7
Contents 6033 Congratulations SpecificationsBurning Solid Fuels Safety StepsBurning Solid Fuels Clearances to Combustibles Installation RequirementsGuidelines for Exhaust Venting Systems Design Clearances to CombustiblesGuidelines for Exhaust Venting Systems Design Design Guidelines for Outside Combustion AIR Connection Mobile Home Installation Requirements Installation ConfigurationsOutside Wall Termination Alcove Installation RequirementsALCOVE-THROUGH the Wall Installation Requirements Corner InstallationHorizontal Exhaust Termination Freestanding Stove Installation RequirementsInside Vertical Pipe with Roof Termination Ussc Cleaning the Glass Glass MAINTENANCE, Removal and ReplacementRemoval of Broken or Damaged Ceramic Glass Stove Controls Damper Control Function Lighting InstructionsCircuit Board Functions Disposal of AshesDisposal of Ashes Maintenance Instructions Setting the DraftSoot and Flyash Formation and Need for Removal Spring Cleaning Maintenance InstructionsHopper Auger Safety Switch Location Automatic Safety FeaturesRear View Side View Fuel Additive Thermostat InstallationUnplug stove before preforming any maintenance work Trouble ShootingTrouble Shooting Opening with latex or an inexpensive Wiring Diagram Repair Repair Parts LIST-6033 HOW to Order Repair Parts