
Locating the New Water Heater (cont’d)
Facts to Consider About the Location (cont’d)
WARNING
Do not install in a confined area such a closet, unless you provide ventilation air as shown in the “Locating The New Water Heater” section. Never obstruct the flow of ventila- tion air. If you have any doubts or questions at all, call your gas company. Failure to provide ventilation air can result in a fire or explosion and can cause DEATH, SERIOUS BODILY INJURY, OR PROPERTY DAMAGE.
•The venting system must be installed in a manner which allows inspection of the installation of the venting pipes and joints as well as periodic inspection after installation as required by the National Fuel Gas Code ANSI Z223.1.
WARNING
Vent termination must not be within 4 feet of any items such as gas meters, gas valves or other gas regulating equipment.
WARNING
If this water heater will be used in beauty shops, barber shops, cleaning establishments, or
WARNING
Failure to have required clearances between water heater and combustible material will result in a fire hazard.
Combustion Air and Exhaust
WARNING
When determining the installation location for a power direct vent water heater, snow accumulation and drifting should be considered in areas where applicable.
Venting Through an Outside Wall – Clearances
•0″ clearance for 3″ PVC, ABS, or CPVC Schedule 40 piping from combustible surfaces.
•18″ minimum in all directions from any obstruction, such as a wall, that may interfere.
•12″ minimum from the ground and corners, 9″ ceiling overhangs. Figure 2.
•The Power Direct Vent outlet terminal shall terminate at least 36″ above any forced air inlet located within 10 feet. Figure 3.
•The Power Direct Vent outlet terminal of 50,000 BtuH input mod- els or less shall terminate at least 9″ below, 9″ horizontally from or 9″ above any door, window or gravity air inlet into the building. Figure 3.
•The Power Direct Vent outlet terminal of over 50,000 BtuH input models shall terminate at least 12″ below, 12″ horizontally from or 12″ above any door, window or gravity air inlet into the building. Figure 3.
•18″ minimum from other natural draft (gravity) direct vent, power vent or power direct vent appliance inlet and/or outlet vent(s) when directly above or 135° to either side of center line. Figure 4, page 9.
•24″ minimum from any appliance inlet and/or outlet vents when directly below or 45° to either side of center line. Figure 4, page 9.
•The location selection must provide clearances for servicing and proper operation of the water heater. Figure 5.
•Vent termination must not be within 4 feet of any items such as gas meters, gas valves or other gas regulating equipment.
Figure 2
A
A
A
PDV
TERMINAL
12″ min.
Figure 3
A - 9″ min. (50,000 BtuH input models or less)
A - 12″ min. (over 50,000 BtuH input models)
9″ min. from any overhang
C
Lof Flue
12″ min.
| PDV |
| TERMINAL |
| “B” |
A | 36″ min. IF “B” DIMENSION |
| IS LESS THAN 120″ |
| FORCED AIR |
| INLET |
| GRADE |
| CORNER INSTALLATION |
| OF INLET AND OUTLET |
| NOT RECOMMENDED |
8