QHT B3-B9 installation instructions Wiring

Page 23

11. Wiring

The electricity to the boiler shall come from a dedicated breaker in the electric service box. A service switch should be mounted on the side of the boiler so the burner technician can service the burner and controls. The electrical wiring should be routed so as not to interfere with normal servicing of the boiler. Wiring done in the field between devices not attached to boiler shall conform with the temperature limitations for type T wire (63F/35C) or other specified wire as applicable when installed in accordance to manufacturer's instructions and wiring diagrams.

If an external electrical source is utilized, the boiler, when installed, must be electrically bonded to ground in accordance with the requirements of the authority having jurisdiction or, in the absence of such requirements, with the National Electrical Code, ANSI/NFPA 70 and/or the Canadian Electrical Code Part 1, CSA C22.1, Electrical Code.

Since the boiler is equipped with a swinging burner door, the supplied 48” long burner wiring harness with 4-prong quick disconnect plug needs to be used. The short end of the wiring harness needs to be wired to the burner following the respective burner wiring diagram in the subsequent pages of this manual. The long end of the wiring harness needs to be wired into the burner service switch located at the installers discretion.

Refer to pages 19 to 23 for oil wiring diagrams and pages 24 to 25 for gas wiring diagrams.

Page 23

Image 23 Contents
Phone FAX Manufactured by Biasi S.p.A Verona, Italy Distributed ByPage Table of Contents Please read this page carefully Important InformationPage To Start UP the Appliance Homeowner Information for GasGas systems only General InformationTrim Kit Components Do not Over Tighten Draw Rods Boiler Block AssemblyBoiler Location Switch Gas systems only Installation of Boiler Trim ComponentsBoiler Tapping Diagram Installation of Boiler Trim ComponentsPiping the Boiler Safety Relief ValveIntake Venting Figure a Common Exhaust Venting Exhaust VentingBlocked Flue Switch Gas Venting Gas Burner SetupOil Burner Manufacturer Oil Burner SetupGas Burner Setup Gas Line Piping Installation of Sediment Trap and Burner SupplyBoiler Jacket Assembly Wiring 7248U Wiring Procedure Oil Burner Wiring Riello OIL BURNER, SR504, Control Wiring with DHW Priority Riello OIL BURNER, AZ-4P, Control Wiring with DHW Priority Carlin OIL BURNER, SR501, Control Wiring with DHW Priority Page Heatwise SU-2A, SR503, Control Wiring with DHW Priority Page Commissioning MaintenanceSystem Checkout Installer NotesPage Page Tear on this Line