Smith Cast Iron Boilers GS110W General Venting Guidelines, General Direct Vent Info

Page 10

Page 10

GS110 DIRECT VENT BOILER INSTALLATION AND OPERATION INSTRUCTIONS

GENERAL VENTING GUIDELINES

WARNING: The vent installation must be in accordance with Part 7, Venting of Equipment, of the National Fuel Gas Code, ANSI Z223.1/ NFPA 54-latest revision or applicable provisions of the local building codes. Canadian installations must comply with CSA B149.1 or

.2 Installation Code. Improper venting can result in excessive levels of carbon monoxide which can result in severe personal injury or death!

WARNING: Thimbles and fire-stops must be used where required. A minimum clearance of 6" must be maintained between single wall metal vents and combustible construction or a fire resulting in severe personal injury or death may occur!

WARNING : Each boiler/water heater must have it's own vent system. Common positive pressure vent systems are not to be used! Improper installation can result in excessive levels of carbon monoxide which can cause severe personal injury or death!

All vent systems must be fully supported by the building structure and not by the boiler/water heater.

Certified vent systems are manufactured by the following companies:

Heat-fab, Inc.

130 Industrial Blvd., Turners Falls, MA 01376

(800) 772-0739.

Z-Flex U.S., Inc.

20 Commerce Park North, Bedford, NH 03110-6911

(800) 654-5600.

Protech Systems Inc.

26 Gansevoort Street, Albany, NY 12202

(518) 463-7284

GENERAL DIRECT VENT INFO

In this configuration the boiler blower is used to push the flue products to the outdoors while drawing combustion air from the outdoors. The instructions under the COMBUSTION AIR & VENTILATION SECTION must be followed! The vent system must be sized per Table 3.

Table 3 - Positive Pressure Vent System Sizing

Boiler

Equivalent Vent

Equivalent Vent

Model

Length (see note)

Length (see note)

Number

3” Diameter

4” Diameter

 

 

 

GS110-3

45 feet (13.7 m)

*65 feet (19.8 m)

GS110-4

45 feet (13.7 m)

*65 feet (19.8 m)

GS110-5

45 feet (13.7 m)

*65 feet (19.8 m)

GS110-6

n/a

40 feet (12.2 m)

GS110-7

n/a

40 feet (12.2 m)

VENT SYSTEM OPTIONS

The GS110 may be vented the following ways:

1)Direct Vent (Positive Pressure), uses a vent system certified to UL 1738 for installations in the United States, ULS636 for installations in Canada. Combustion air is piped from the outdoors to the blower inlet.

2)Horizontal Vent (Positive Pressure), uses a vent system certified to UL 1738 for installations in the United States, ULS636 for installations in Canada. Combustion air is obtained from the space in which the unit is installed.

3)Vertical Vent (Positive Pressure), uses a vent system certified to UL 1738 for installations in the United States, ULS636 for installations in Canada. Combustion air is piped from the outdoors to the blower inlet or is obtained from the space in which the unit is installed.

4)Vertical/Chimney Vent (Negative Pressure), uses an approved metal chimney system or masonry chimney. Combustion air is obtained from the space in which the unit is installed or is piped from the outdoors to the blower inlet.

* 4" to 3" reducer required

Note: Subtract 5 feet (1.5 m) for each 90° elbow.

HORIZONTAL DIRECT VENT

SYSTEMS

See figures 7 & 8. The vent materials used in horizontal positive pressure vent systems must be certified to UL 1738 for installations in the United States, ULS636 for installations in Canada.

Each 90° elbow is equal to 5 linear feet (1.5 m) of pipe. To maximize the performance of single wall sheet metal vent systems locate 90° elbows as far from the boiler as possible and from one another. For best results, horizontal vent systems should be as short and straight as possible. The vent system must be both gas tight and watertight. All seams and joints in metal pipes must be joined and sealed in accordance with the vent system manufacturer’s instructions.

When horizontal vent runs exceed 5 feet (1.5m) they must be supported at 3 foot (0.98 m) intervals with overhead hangers. The vent system must be pitched down, toward the vent terminal, 1/4" per foot (21mm per meter). If any part of a single wall metal vent system passes through an unheated space it must be insulated with insulation rated for 400°F. Structural penetrations must be made using approved thimbles.

Image 10
Contents GS110W Contents Before YOU StartBoiler Ratings & Capacities Boiler LocationCombustion AIR & Ventilation All Combustion Air From Inside The BuildingCombustion Air Duct Sizing Duct SizeCombustion Air System Sizing NumberIntake Air Option Vertical Guidelines Intake Air Optional Horizontal GuidelinesSmith Page Vent System Options General Venting GuidelinesGeneral Direct Vent Info Horizontal Direct Vent SystemsCertified Vent & Intake Terminals Vertical Direct Vent SystemsHorizontal Vent Positive Pressure Systems Certified Vent TerminalsChimney Inspection & Sizing Vertical Vent Positive Pressure SystemsVertical Vent Negative Pressure Systems Equivalent Breeching & Chimney SizeVertical Positive Pressure Venting Cat Common Vent Systems Condensate Piping Boiler Water VolumeHeating System Piping System Bypass Bypass PipingPump Away Bypass Piping For Use With Cooling Units CirculatorsGAS Supply Piping Equivalent Pipe Length ChartWhen servicing controls. Wiring errors can cause Gas Pipe CapacityOperational Sequence Thermostat InstallationControl Outputs Wiring Connection Diagram Wiring Ladder Diagram For Your Safety Read Before Operating Pour Votre Sécurité Lisez Avant DE Mettre EN Marche Boiler Operation Boiler SET UPDirect Ignition System Boiler Checking & Adjustment Air and Manifold PressureBoiler Maintenance Instructions to the Installer Page Service and Replacement Parts List Model Size with Item Quantities Below Ref # Name of PartModel Size with Item Quantities Below Page North ELM Street WESTFIELD, MA 01085 TEL 562-9631 FAX 413

GS110W specifications

The Smith Cast Iron Boilers GS110W stands as a premier choice for those seeking efficiency and reliability in heating systems. Known for their robust construction and advanced engineering, Smith Boilers are designed to meet the needs of both residential and commercial applications. The GS110W model showcases an impressive blend of performance and durability, making it a favorite among HVAC professionals and end users alike.

One of the main features of the GS110W is its cast iron construction. Cast iron is celebrated for its ability to retain heat, allowing the boiler to operate efficiently while providing consistent warmth over extended periods. This material also contributes to the boiler's longevity, allowing it to withstand the rigors of heating without significant wear and tear. The GS110W is designed to last, making it a wise investment for any heating needs.

The GS110W boasts an output capacity of 110,000 BTU/hour, making it suitable for a variety of heating applications. This output enables it to efficiently heat large spaces, whether in a multi-story building or a spacious home. The boiler’s efficiency rating is further enhanced by its ability to use multi-fuel options. It can efficiently burn oil or gas, providing flexibility depending on the availability and cost of fuel.

In terms of technology, the GS110W incorporates advanced boiler design that includes a submerged combustion chamber. This engineering feature allows for superior heat transfer while minimizing heat loss, ensuring that the maximum amount of energy is utilized for heating. Additionally, the boiler features a low water cutoff to enhance safety, preventing potential overheating and system failures.

Reliability is further ensured through the GS110W’s built-in controls and adjustments. The boiler is equipped with a digital aquastat that allows for precise temperature management, ensuring optimal performance. This user-friendly feature makes it easier for homeowners and technicians to monitor system conditions and make necessary adjustments for peak efficiency.

Another noteworthy characteristic of the Smith Cast Iron Boilers GS110W is its low emissions output. As environmental considerations become increasingly important, the GS110W is designed to minimize its environmental impact while still delivering powerful heating capabilities.

In conclusion, the Smith Cast Iron Boilers GS110W offers an outstanding combination of durability, efficiency, and advanced technology. Its robust cast iron construction, multi-fuel capability, and innovative design features make it a top choice for anyone looking to enhance their heating system. For those in search of reliable and efficient heating solutions, the GS110W stands out as a formidable contender.