Page 12 | GT INSTALLATION AND OPERATION INSTRUCTIONS |
Understand and follow the plumbing requirements provided in this section. Keep serviceability in mind when installing plumbing around the boiler cabinetry. Install fi ttings that will allow the system to be fl ushed if needed during annual
Hot water boilers are designed to operate with airless water in the system. The GT boiler is provided with a 1/8 in, 3 mm, air vent located on the top of the unit. This air vent is intended to vent the boiler on initial startup. This device will NOT continuously vent air collecting in the primary loop and is not intended to be the primary venting device. The air scoop as shown in Figure 21 is the primary venting location. It is recommended that an additional air scoop be used in the secondary plumbing. If air continues to be a problem an air scrubber must be used.
NOTE: Only inhibited propylene glycol solutions should be used if freeze protection is required. Avoid using mixtures greater than 30%, unless the size of the boilers’ circulator(s) is increased accordingly. Under no circumstances should a 50% mixture be exceeded.
Pressure Relief Valve
Each boiler is equipped with a 30 psi pressure relief valve that must be piped in accordance with the ANSI/ ASME Boiler and Pressure Vessel Code, Section IV to prevent scalding of persons with hot liquid or vapor in the event of a discharge, see Figure 20.
Support the relief valve discharge piping to prevent strain on the valve body. Leave the open end of the relief valve discharge pipe visible for periodic inspection.
NOTE: The discharge pipe diameter must be the same at the relief valve output diameter. Never restrict the outlet relief valve.
WARNING: Never install any type of valve between the boiler and the relief valve or an explosion causing extensive property damage, severe personal injury or death may occur!
Figure 20 - Relief Valve Piping
Non ASME | All ASME Models |